CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
122
BACnet PIC Statement
The BACnet Feature
Standard Object Types Supported - Life Safety Point/Life Safety Zone
Present Value
BACnet
Enumeration
BACnet
LifeSafetyState
Fire Panel State
0
IssQuiet
Normal
1
IssPreAlarm
PreAlarm
2
IssAlarm
Fire Alarm, Security Alarm
(Life/Property), Critical Process
Alarm, (Life/Property), Medical
Emergency, IB Smash Glass, Panic
Alarm
3
IssFault
Security Trouble, Fire Trouble, Non-
Fire Trouble, Fire Device or Zone,
Disabled, Non-Fire Device Disabled
7
IssActive
Non-Fire Activation
22
IssSupervisory Supervisory (Equipment),
Supervisory (Guard's Tour)
Tracking
Value
BACnet
Enumeration
BACnet
LifeSafetyState
Fire Panel State
0
IssQuiet
Normal
1
IssPreAlarm
PreAlarm
2
IssAlarm
Fire Alarm, Security Alarm
(Life/Property), Critical Process
Alarm (Life/Property), Medical
Emergency, IB Smash Glass, Panic
Alarm
3
IssFault
Security Trouble, Fire Trouble, Non-
Fire Trouble, Fire Device or Zone,
Disabled, Non-Fire Device Disabled
7
IssActive
Non-Fire Activation
22
IssSupervisory Supervisory (Equipment),
Supervisory (Guard's Tour)
Event State
BACnet
Enumeration
BACnet Event
State
Fire Panel State
0
EsNormal
Normal
1
EsFault
Security Trouble, Fire Trouble, Non-
Fire Trouble, Fire Device Disabled,
Non-Fire Device Disabled
2
EsOffNormal
All statuses other than normal and
fault.
Reliability
BACnet
Enumeration
BACnet
Reliability
Fire Panel State
0
reNoFaultDete
cted
All statuses other than trouble.
7
re_UnreliableOt
her
Security Trouble, Fire Trouble, Non-
Fire Trouble