
CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
118
To Connect with the BACnet Client
The BACnet Feature
11.Find and click
BACnet Settings
in the
CLSS Gateway mainboard Settings
section.
12.Specify the required values as in the below table:
Fields
Action
Enable BACnet
functionality
Select to enable the BACnet application.
Notification Type
Select Life Safety or Multi-state suitable to the customer
requirement.
Network Number
Specify a network number of this BACnet CLSS Gateway
mainboard. It helps to identify the CLSS Gateway mainboard
when multiple CLSS Gateway mainboards are in the network.
Note: Sometimes two or more CLSS Gateway mainboards in
the same network might use the BACnet feature. Each of
them should have its own unique network number. Ensure
that the difference between any two network numbers is at
least 100.
BACnet Port
Specify the BACnet port.
The universal default port number is 47808.
Its range can be: 47808 - 47823 (0xBAC0 - 0xBACF)
Object Addressing
Select the addressing type. Options: IFOM Addressing or
Flexible Addressing.
Note: Flexible addressing is available only for Gent panels.
FOREIGN DEVICE CONFIGURATION
Foreign Device
Select to enable the foreign device.
IP Address
Enter the BBMD Server IP address.
Port
Enter the BBMD Port number.
Register Time
Specify the time in seconds. As per this value, the device will
periodically re-register with the BBMD to maintain full
participation in the BACnet/IP network.
Note: Maximum value is 30 seconds.