CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
120
Replacing the BACNET-GW
The BACnet Feature
13.Click
SAVE
.
8.11 Replacing the BACNET-GW
The CGW-MB and the BACNET-GW-3 have different addressing schemes. Refer to the
section for the supported objects details.
Ensure that the replacing CGW-MB has correct object addresses and the old object
mappings of BACNET-GW-3 are removed.
Refer to the
section for the CGW-MB object addressing details.
1. Ensure that the BACnet feature in the CGW-MB is licensed.
2. Go to CGW-MB Web Configuration Tool.
3. Click the
BACnet Settings
tab.
4. Ensure that the below BACnet settings are same in the CGW-MB:
• Static IP address
• BACnet Port Number
• Foreign device configurations
• Node mapping
• Network Number
5. Delete the replaced BACnet CLSS Gateway mainboard related objects on the BACnet
client.
6. Connect the CGW-MB.
7. Rediscover the BACnet objects.
Or
Restart the BACnet client.
8. Modify the client graphics according to the rediscovered objects.
8.12 Using Both the CGW-MB and the Legacy BACnet CLSS Gateway
mainboard
The CGW-MB and the BACNET-GW-3 have different addressing schemes. Ensure that
they are assigned with their own addressing scheme.
Refer to the
section for the CGW-MB object addressing details.
1. Ensure that the BACnet feature in the CGW-MB is licensed.
2. Go to CGW-MB Web Configuration Tool.
3. Click the
BACnet Settings
tab.
4. Configure the BACnet settings in the new CGW-MB.
Refer to the
To Configure the BACnet Settings
section for the configuring procedure.
5. Connect the CGW-MB and rediscover the BACnet objects.
6. Modify the client graphics according to the new instance numbers (object addresses).
Fields
Action
Equipment Supervision
and Monitoring
Click to set Priorities of Events
General Alarm
Click to set Priorities of Events
Fire Supervision
Click to set Priorities of Events
Process Trouble
Click to set Priorities of Events
System Status Active
Click to set Priorities of Events
Set to default
Click to set the priorities to default