CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
56
CGW-MB Control Features
Modbus Communications
For NOTIFIER UL
Table 7.13: Zone Commands
Table 7.9: Point Commands
Command
Value
Holding Register
Acknowledge Point
0x0200
Use Device/Module
Holding Register
Address
Acknowledge Block
0x0300
Enable
0x0400
Disable
0x0500
Activate*
0x0800
Deactivate*
0x0900
Acknowledge Trouble
0x0b00
Acknowledge Alarm
0x0c00
Acknowledge CO and Gas
Alarm
0x0d00
Table 7.10: Zone Commands
Command
Value
Holding Register
Enable
0x0400
Use Device/Module Holding
Register Address
Disable
0x0500
Activate*
0x0800
Deactivate*
0x0900
Table 7.11: Node Commands
Command
Value
Holding Register
Reset
0x0001
20001
Silence
0x0002
Table 7.12: Point Commands
Command
Value
Holding Register
Acknowledge
0x0100
Use Device/Module Holding Register
Address
Disable
0x0200
Enable
0x0400
Activate
0x0800
Deactivate
0x1000
Command
Value
Holding Register
Disable
0x0200
Use Zone Holding Register Address
Enable
0x0400
Activate
*
0x0800
Deactivate
*
0x1000
*
Activate and Deactivate work only for output-controlled modules like
control and relay.
Different panels support different zone types. Refer to
Command Availability by Panel”
for information about zone types
supported.