CGW-MB Installation and Users’ Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
125
BACnet PIC Statement
The BACnet Feature
Event State
BACnet
Enumeration
BACnet Event
State
Fire Panel State
0
EsNormal
Normal
1
EsFault
Security Trouble, Fire Trouble, Non-
Fire Trouble, Fire Device Disabled,
Non-Fire Device Disabled
2
EsOffNormal
All statuses other than normal and
fault.
Reliability
BACnet
Enumeration
BACnet
Reliability
Fire Panel State
0
reNoFaultDet
ected
All statuses other than trouble.
7
re_Unreliable
Other
Security Trouble, Fire Trouble, Non-
Fire Trouble
Status Flags
Boolean
BACnet Status
Flags
Fire Panel State
0,0,0,0
Normal
Normal
1,0,0,0
InAlarm
Fire Alarm, Security Alarm
(Life/Property), Critical Process
Alarm (Life/Property), Medical
Emergency, PreAlarm, IB Smash
Glass, Panic Alarm
0,1,0,0
Fault
Security Trouble, Fire Trouble, Non-
Fire Trouble
0,0,0,1
OutOfService Fire Device or Zone Disabled, Non-
Fire Device Disabled
1,0,0,1
InAlarm,
OutOfService
If device is in Alarm state (Fire Alarm,
Security Alarm (Life/Property),
Critical Process Alarm
(Life/Property), Medical Emergency,
PreAlarm, IB Smash Glass, Panic
Alarm) and also device goes to
disable state(Fire Device or Zone
Disabled, Non-Fire Device Disabled)
0,1,0,1
Fault,
OutOfService
If device is in trouble state (Security
Trouble, Fire Trouble, Non-Fire
Trouble )and also device goes to
disable state(Fire Device or Zone
Disabled, Non-Fire Device Disabled)
Out of Service
Boolean
Fire Panel State
0
FALSE
All statuses other than disable
1
TRUE
Fire Device or Zone Disabled, Non-