7810iR Internet Communication Module Installation and Setup Guide
5-4
Action Screen
Display
3. Alarm message sent to LRR Line Card,
local message pushed into History Window.
Fail to Manual
UL
Fail to Manual Mode cannot be used with UL installations.
If Fail to Manual is selected and there is a loss of communication between the 7810iR and
the LRR Line Card, an incoming message will be reported as undeliverable to AlarmNet
after approximately 30 seconds. AlarmNet will then route all messages to the secondary CS.
Action Screen
Display
1. Loss of Line Card communication with
Fail to Manual feature selected. Operator
must manually respond to incoming alarms.
2. Loss of Line Card communication with
Fail to Manual feature NOT selected. All
messages from AlarmNet will be bounced.
AlarmNet will route all message traffic for this
CS to the Backup Account CS.