Intesis
TM
KNX
– Mitsubishi Heavy Industries AC
User’s Manual r1.2 eng
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
23 / 26
2.- Check Intesis
TM
LED status:
LED
Status
Explanation
Solution
OP
Off
No power reaching the
internal device
Check power connection
Check fuse status
(
see part 13 in Figure 3.2
ERR
Blinking once
periodically
Superlink
communication failure
Check Superlink cables and terminals
(connectors, length of cables, etc.)
HOST
Off
Configuration error
Download the binary file again
(see 4.3)
PAC
Off
Communication error in
the Superlink network
Check the Mitsubishi Heavy Industries
Superlink network and its connections
Table 6.1
Intesis
TM
LED status information
6.3.2
Software checking
Once physical connections have been checked, if functioning problems still remain, please
use the LinkBoxEIB tool to monitor the working status of the device.
•
To check the KNX communication status, click on the
KNX
button in the
menu
bar
(see Figure 4.1).
•
To check the MHI communication status, click on the
MHI
button, also in the
menu bar
(see Figure 4.1).
•
To check the signal values in the KNX communication objects, click on the
Signals
button, also in the
menu bar
(see Figure 4.1).
Further information regarding the monitoring procedure and the information provided in
each window can be consulted in the LinkBoxEIB Manual.