Intesis

TM

 KNX 

– Mitsubishi Heavy Industries AC 

 

 

User’s Manual r1.2 eng

 

    

 

  

 

 

 

 

 

© HMS Industrial Networks S.L.U - All rights reserved 

This information is subject to change without notice

 

 

  URL    https://www.intesis.com  

 
 

                19 / 26

 

7.2

 

W:

 Indicates if this signal is allowed to be written from KNX system 

(“W” 

flag activated, “blank” flag not activated)

.

 

7.3

 

T:

  Indicates  if  this  signal  will  generate  a  telegram  sending  to  the  KNX 

system following a change of the signal’s value, that is to say, any change 

of value of this signal in MHI side will be transmitted to the KNX system if 
this flag is activated 

(“T” flag activated, “blank” flag not activated)

.

 

7.4

 

U:

  Indicates  if  this  signal  will  be  updated  (sending  read  requests) 

whenever  Intesis

TM

 starts up or after a KNX bus reset 

(“U” flag activated 

for  the  main  group  address,  “U2”  activated  for  the  listening  group 
address, “blank” flag not activated).

1

 

8.

 

Active:

  Indi

cates  if  the  signal  is  active  or  not  for  the  current  configuration  (“1

-

Yes” signal active, “0

-

No” signal not active).

 

 

See section 2.2 for further detail on available signals and the possible values on each one. 

 

 

Sending the configuration to Intesis

TM

 

 
When the configuration is finished, follow the next steps. 
 
 

1.- Click on 

Save

 button to save the project to the project folder on your hard disk 

 

(more information in LinkBoxEIB User Manual).  

 
 

2.- You will be prompted to generate the configuration file to be sent to the gateway. 

 

 

a.- If 

Yes

 is selected, the binary file (MHI.Lbox) containing the configuration 

 

 

     for the gateway will be generated and saved also into the project folder. 

 

 

b.- If 

NO

 is selected, remember that the binary file with the project needs to 

 

 

     be generated before the Intesis

TM

 starts to work as expected. 

 
 

3.- Once in the configuration window again, click on 

exit

. Configuration file is ready 

 

to be sent to the Intesis

TM

 device. 

 
 

4.-  Press  the 

Send  File

  button  to  send  the  binary  file  to  the  Intesis

TM

  device.  The 

 

process  of  file  transmission  can  be  monitored  in  the  Intesis

TM

  Communication 

 

Console  window.  Intesis

TM

  will  reboot  automatically  once  the  new  configuration  is 

 

loaded.  

 

After any configuration change, do not forget to send the configuration file 
to the Intesis

TM

 using button Send File. 

 
 

 

Signals viewer 

 
Once the gateway is running with the correct configuration, to supervise the status of the 
configured signals, press the 

Signals

 button on the 

menu 

bar (see Figure 4.1). The Signals 

Viewer window will open (see Figure 4.7).  
 
This  window  shows  all  signals  active  within  the  gateway  with  its  main  configuration 
parameters and its real time value

2

 in the 

Value

 column. 

                                           

1

 

DO  NOT  BE  CONFUSED:  Philosophy  of  Intesis

TM

  point's  U  flag  is  not  the  same  as  KNX  device's  U  flag.  In  KNX 

devices, U flag means that the point's value will be updated whenever a write telegram for the group address is 

received by the device.

 

2

 

In  case  you  connect  to  the  Intesis

TM

 

when  it’s  been  run

ning  for  a  certain  time,  you  should  press  the 

Refresh

 

button  to  get  updated  values.  After  pressing 

Refresh

,  all  signal  values  will  keep  continuously  updated  until  the 

connection is closed.

 

Содержание Intesis INKNXMHI048O000

Страница 1: ...Gateway for integration of Mitsubishi Heavy Industries air conditioning systems into KNX TP 1 EIB control systems Application s Program Version 2 1 USER MANUAL Issue date 07 2012 r1 2 ENGLISH...

Страница 2: ...purposes and are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many...

Страница 3: ...rights reserved This information is subject to change without notice URL https www intesis com 3 26 Gateway for integration of Mitsubishi Heavy Industries air conditioning systems into KNX TP 1 EIB co...

Страница 4: ...tesisTM Device Connections 12 Connect to Mitsubishi Heavy Industries Interface 13 Connect to KNX Interface 14 Connect to PC LinkBoxEIB 14 Power Device 14 LinkBoxEIB Configuration monitoring tool for I...

Страница 5: ...he KNX system read and write in the communication objects Moreover IntesisTM includes all hardware required to manage control Mitsubishi Heavy Industries indoor units without extra components needed I...

Страница 6: ...m the corresponding action in the MHI s AC system In the continuous polling if no response is detected the corresponding virtual signal inside the gateway will be activated indicating communication er...

Страница 7: ...nk or Superlink II New Superlink Indoor Unit actual address range is 00 to 47 INKNXMHI128O000 Model supporting up to 128 indoor units For Superlink II New Superlink Indoor Unit actual address range is...

Страница 8: ...ew value is updated to the bus by sending a write telegram addressed to its associated group address The rest of KNX devices in the installation that have a communication object associated to this gro...

Страница 9: ...float 32bit floating type EIS10 16bit Counter 16bit raw EIS11 32bit Counter 32bit raw EIS13 ASCII char 8bit raw EIS14 8bit Counter 8bit raw ETS3 or ETS4 software tools are not used to configure Intes...

Страница 10: ...cument Write If the option of virtual ambient temperature and SetPoint is activated to be configured from extern KNX sensor see in section 4 2 1of this document Fan Speed 14 Counter 8bit R W Fan Speed...

Страница 11: ...an 4 Dry DPT 20 105 8bit R W Operation Mode 0 Auto 1 Heat 3 Cool 9 Fan 14 Dry DPT 1 100 1bit R W Operation Mode 0 Cool 1 Heat Mode_All Cool 1 Switching 1bit R W 0 Inactive 1 Active Only one of these o...

Страница 12: ...erface connector s description 1 KNX configuration Port C1 8 Reset button Non supported 2 Non supported C2 9 Superlink selector SLK New Superlink II Old Superlink I 3 Console serial port EIA232 10 A B...

Страница 13: ...ded for Superlink connection For prevention of electromagnetic noise malfunctions parallel wiring with the power line should be avoided Select the appropriate Superlink mode in the SLK selector If you...

Страница 14: ...ser Manual Two methods to connect to the PC can be used Ethernet Using the ETH port Figure 3 1 of IntesisTM How to check connectivity is explained in section 6 3 Serial cable Connect the IntesisTM dev...

Страница 15: ...l be covered Connections configuration To configure the IntesisTM connection parameters and to see the points list press on the Config button in the menu bar see Figure 4 1 The Mitsubishi Heavy Indust...

Страница 16: ...lay after a bus reset It is expressed in seconds IntesisIP interface configuration parameters Figure 4 4 IntesisIP interface configuration 1 IP Enter the KNX physical address for the gateway 2 NetMask...

Страница 17: ...expressed in seconds s and ranges can vary from 60 s to 600 s 9 Virtual ambient temperature and setpoint Meant to be enabled when you want the temperature provided by a KNX sensor to be the reference...

Страница 18: ...ossible signal codes 3 Signal Signal s descriptive name optional Useful to identify the signal The default descriptive name corresponds to the signal s code but can be edited or modified 4 EIS KNX dat...

Страница 19: ...binary file MHI Lbox containing the configuration for the gateway will be generated and saved also into the project folder b If NO is selected remember that the binary file with the project needs to b...

Страница 20: ...ing the system In order to force a specific value to a signal double click its row in the table This will display a dialog in which the desired value can be entered see Figure 4 8 Changing its value i...

Страница 21: ...older containing these files in external media once the installation process is finished This way you will be able to do future configuration changes in case of reinstallation of LinkBoxEIB due for ex...

Страница 22: ...esired installation site For your convenience check external enclosure measures see 7 before deciding where to place the IntesisTM device 3 Connect the communication cable coming from the KNX bus to t...

Страница 23: ...ation error in the Superlink network Check the Mitsubishi Heavy Industries Superlink network and its connections Table 6 1 IntesisTM LED status information 6 3 2 Software checking Once physical connec...

Страница 24: ...to change without notice URL https www intesis com 24 26 Mechanical Electrical characteristics 1 Device can be installed in any position 5 mm 195 mm 138 mm 10 mm 15 mm Figure 7 1 External dimensions P...

Страница 25: ...R HOST PAC Push buttons 1 x Reset Device Selectors 1 x SLK selector Console port EIA232 DB9 female DCE SELV Configuration Via console port 2 Firmware Allows upgrades via console port Operational tempe...

Страница 26: ...e on power supply at primary side 33 E33 Inverter primary current error 35 E35 Cooling overload operation 36 E36 Discharge pipe temperature error 37 E37 Outdoor heat exchanger temperature thermistor a...

Отзывы: