7.2
W:
Indicates if this signal is allowed to be written from KNX system
(“W”
flag activated, “blank” flag not activated)
.
7.3
T:
Indicates if this signal will generate a telegram sending to the KNX
system following a change of the signal’s value, that is to say, any change
of value of this signal in MHI side will be transmitted to the KNX system if
this flag is activated
(“T” flag activated, “blank” flag not activated)
.
7.4
U:
Indicates if this signal will be updated (sending read requests)
whenever Intesis
TM
starts up or after a KNX bus reset
(“U” flag activated
for the main group address, “U2” activated for the listening group
address, “blank” flag not activated).
1
8.
Active:
Indi
cates if the signal is active or not for the current configuration (“1
-
Yes” signal active, “0
-
No” signal not active).
See section 2.2 for further detail on available signals and the possible values on each one.
Sending the configuration to Intesis
TM
When the configuration is finished, follow the next steps.
1.- Click on
Save
button to save the project to the project folder on your hard disk
(more information in LinkBoxEIB User Manual).
2.- You will be prompted to generate the configuration file to be sent to the gateway.
a.- If
Yes
is selected, the binary file (MHI.Lbox) containing the configuration
for the gateway will be generated and saved also into the project folder.
b.- If
NO
is selected, remember that the binary file with the project needs to
be generated before the Intesis
TM
starts to work as expected.
3.- Once in the configuration window again, click on
exit
. Configuration file is ready
to be sent to the Intesis
TM
device.
4.- Press the
Send File
button to send the binary file to the Intesis
TM
device. The
process of file transmission can be monitored in the Intesis
TM
Communication
Console window. Intesis
TM
will reboot automatically once the new configuration is
loaded.
After any configuration change, do not forget to send the configuration file
to the Intesis
TM
using button Send File.
Signals viewer
Once the gateway is running with the correct configuration, to supervise the status of the
configured signals, press the
Signals
button on the
menu
bar (see Figure 4.1). The Signals
Viewer window will open (see Figure 4.7).
This window shows all signals active within the gateway with its main configuration
parameters and its real time value
2
in the
Value
column.
1
DO NOT BE CONFUSED: Philosophy of Intesis
TM
point's U flag is not the same as KNX device's U flag. In KNX
devices, U flag means that the point's value will be updated whenever a write telegram for the group address is
received by the device.
2
In case you connect to the Intesis
TM
when it’s been run
ning for a certain time, you should press the
Refresh
button to get updated values. After pressing
Refresh
, all signal values will keep continuously updated until the
connection is closed.