background image

Intesis

TM

 KNX 

– Mitsubishi Heavy Industries AC 

 

 

User’s Manual r1.2 eng

 

    

 

  

 

 

 

 

 

© HMS Industrial Networks S.L.U - All rights reserved 

This information is subject to change without notice

 

 

  URL    https://www.intesis.com  

 
 

                17 / 26

 

x in “

Indoor Unit 

xxx”) is the reference that will be used later on (in tab “Signals”) 

to refer to this AC indoor unit. You can also change the  description  name of the 
Indoor  Unit  and  its  address  to  facilitate  integration  tasks  using 

Add

  and 

Name

 

text boxes. 
 

2.

 

Add:

 Enter here the desired Indoor Unit address. 

 

3.

 

Name: 

Enter here the desired descriptive Indoor Unit name (optional). 

 

4.

 

KNX  Datapoint  type  for  HVAC  Mode  communication  object: 

Select  the 

desired codification so the Mode object matches your integration needs. 

 

5.

 

Gateway  version:

  Selection  of  the 

Intesis

TM

  KNX 

  Mitsubishi  Heavy  Industries

 

gateway  you  are  setting  up  (

128AC

  for 

INKNXMHI128O000,

 

48AC

  for 

INKNXMHI048O000

).  

 

6.

 

Timeout  response: 

Maximum  amount  of  time  permitted  before  activating  the 

Communication Error signal. It is expressed in milliseconds (ms) and ranges  can 
vary from 2000 ms to 10000 ms. 

 

7.

 

Delay  interframe:

  Maximum  amount  of  time  permitted  between  End  Of 

Transmission  (EOT)  and  a  new  frame.  It  is  expressed  in  milliseconds  (ms)  and 
ranges can vary from 500 ms to 3000 ms. 

 

8.

 

Monitoring cadence:

 Cadence of monitoring and subscription. It is expressed in 

seconds (s) and ranges can vary from 60 s to 600 s. 

 

9.

 

Virtual  ambient  temperature  and  setpoint: 

Meant  to  be  enabled  when  you 

want  the  temperature  provided  by  a  KNX  sensor  to  be  the  reference  ambient 
temperature  for  the  air  conditioner.  Then,  the  following  formula  applies  for 
calculation of real 

Control_

 

Setpoint Temperature

 sent to the AC unit:

 

 

 
 
 

 
 
 
 

As an example, consider the following situation: 

 

User wants: 

19ºC

 

(“

KNX Setp. Temp

.

”)

 

User sensor (a KNX sensor) reads: 

21ºC

 

(“

KNX Amb Temp

.

”)

 

Ambient temp. read by MHI system is: 

24ºC

 

(“

AC Ret. Temp

”)

 

 
In  this  example,  the  final  setpoint temperature  that  INKNXMHI048O000/128  will 

send out to the indoor unit (shown in “

Setp. Temp

.

”) will become 24ºC –

 (21ºC - 

19ºC) = 

22ºC

. This is the setpoint that will actually be requested to MHI unit. 

 
This  formula  will  be  applied  as  soon  as  the 

Control_  Setpoint  Temperature 

and 

Control_  Ambient  Temperature 

objects  are  written  at  least  once  from  the  KNX 

installation. After that, they are kept always consistent. 

 

Note  that  this  formula  will  always  drive  the  AC  indoor  unit  demand  in  the 

right

 

direction, regardless of the operation mode (Heat, Cool or Auto). Due to the use 
of this functionality, temperature showed in the KNX device and in the MHI remote 
controller (in case it exist) may differ. 

 

 

“AC Setp. Temp” = “AC Ret. Temp” 

(“KNX Amb

Temp.” 

“KNX Setp. Temp”)

 

 

 

AC Setp. Temp: AC indoor unit setpoint temperature 

 

AC Ret. Temp: AC indoor unit return temperature 

 

KNX Amb. Temp.: Ambient temperature provided from KNX 

 

KNX Setp. Temp: Setpoint temperature provided from KNX 

 

Содержание Intesis INKNXMHI048O000

Страница 1: ...Gateway for integration of Mitsubishi Heavy Industries air conditioning systems into KNX TP 1 EIB control systems Application s Program Version 2 1 USER MANUAL Issue date 07 2012 r1 2 ENGLISH...

Страница 2: ...purposes and are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many...

Страница 3: ...rights reserved This information is subject to change without notice URL https www intesis com 3 26 Gateway for integration of Mitsubishi Heavy Industries air conditioning systems into KNX TP 1 EIB co...

Страница 4: ...tesisTM Device Connections 12 Connect to Mitsubishi Heavy Industries Interface 13 Connect to KNX Interface 14 Connect to PC LinkBoxEIB 14 Power Device 14 LinkBoxEIB Configuration monitoring tool for I...

Страница 5: ...he KNX system read and write in the communication objects Moreover IntesisTM includes all hardware required to manage control Mitsubishi Heavy Industries indoor units without extra components needed I...

Страница 6: ...m the corresponding action in the MHI s AC system In the continuous polling if no response is detected the corresponding virtual signal inside the gateway will be activated indicating communication er...

Страница 7: ...nk or Superlink II New Superlink Indoor Unit actual address range is 00 to 47 INKNXMHI128O000 Model supporting up to 128 indoor units For Superlink II New Superlink Indoor Unit actual address range is...

Страница 8: ...ew value is updated to the bus by sending a write telegram addressed to its associated group address The rest of KNX devices in the installation that have a communication object associated to this gro...

Страница 9: ...float 32bit floating type EIS10 16bit Counter 16bit raw EIS11 32bit Counter 32bit raw EIS13 ASCII char 8bit raw EIS14 8bit Counter 8bit raw ETS3 or ETS4 software tools are not used to configure Intes...

Страница 10: ...cument Write If the option of virtual ambient temperature and SetPoint is activated to be configured from extern KNX sensor see in section 4 2 1of this document Fan Speed 14 Counter 8bit R W Fan Speed...

Страница 11: ...an 4 Dry DPT 20 105 8bit R W Operation Mode 0 Auto 1 Heat 3 Cool 9 Fan 14 Dry DPT 1 100 1bit R W Operation Mode 0 Cool 1 Heat Mode_All Cool 1 Switching 1bit R W 0 Inactive 1 Active Only one of these o...

Страница 12: ...erface connector s description 1 KNX configuration Port C1 8 Reset button Non supported 2 Non supported C2 9 Superlink selector SLK New Superlink II Old Superlink I 3 Console serial port EIA232 10 A B...

Страница 13: ...ded for Superlink connection For prevention of electromagnetic noise malfunctions parallel wiring with the power line should be avoided Select the appropriate Superlink mode in the SLK selector If you...

Страница 14: ...ser Manual Two methods to connect to the PC can be used Ethernet Using the ETH port Figure 3 1 of IntesisTM How to check connectivity is explained in section 6 3 Serial cable Connect the IntesisTM dev...

Страница 15: ...l be covered Connections configuration To configure the IntesisTM connection parameters and to see the points list press on the Config button in the menu bar see Figure 4 1 The Mitsubishi Heavy Indust...

Страница 16: ...lay after a bus reset It is expressed in seconds IntesisIP interface configuration parameters Figure 4 4 IntesisIP interface configuration 1 IP Enter the KNX physical address for the gateway 2 NetMask...

Страница 17: ...expressed in seconds s and ranges can vary from 60 s to 600 s 9 Virtual ambient temperature and setpoint Meant to be enabled when you want the temperature provided by a KNX sensor to be the reference...

Страница 18: ...ossible signal codes 3 Signal Signal s descriptive name optional Useful to identify the signal The default descriptive name corresponds to the signal s code but can be edited or modified 4 EIS KNX dat...

Страница 19: ...binary file MHI Lbox containing the configuration for the gateway will be generated and saved also into the project folder b If NO is selected remember that the binary file with the project needs to b...

Страница 20: ...ing the system In order to force a specific value to a signal double click its row in the table This will display a dialog in which the desired value can be entered see Figure 4 8 Changing its value i...

Страница 21: ...older containing these files in external media once the installation process is finished This way you will be able to do future configuration changes in case of reinstallation of LinkBoxEIB due for ex...

Страница 22: ...esired installation site For your convenience check external enclosure measures see 7 before deciding where to place the IntesisTM device 3 Connect the communication cable coming from the KNX bus to t...

Страница 23: ...ation error in the Superlink network Check the Mitsubishi Heavy Industries Superlink network and its connections Table 6 1 IntesisTM LED status information 6 3 2 Software checking Once physical connec...

Страница 24: ...to change without notice URL https www intesis com 24 26 Mechanical Electrical characteristics 1 Device can be installed in any position 5 mm 195 mm 138 mm 10 mm 15 mm Figure 7 1 External dimensions P...

Страница 25: ...R HOST PAC Push buttons 1 x Reset Device Selectors 1 x SLK selector Console port EIA232 DB9 female DCE SELV Configuration Via console port 2 Firmware Allows upgrades via console port Operational tempe...

Страница 26: ...e on power supply at primary side 33 E33 Inverter primary current error 35 E35 Cooling overload operation 36 E36 Discharge pipe temperature error 37 E37 Outdoor heat exchanger temperature thermistor a...

Отзывы: