CompressorStatus
1
–
Switching (1bit)
R
Compressor Status
0
–
Off, 1 - On
FilterSignReset
1
–
Switching (1bit)
W
Filter Sign Reset
1
–
Clear Filter Alarm (When reading always 0)
RemoConErrorReset
1
–
Switching (1bit)
W
Remote Controller Error Reset
1
–
Clear Filter Alarm (When reading always 0)
ThermoOnOff
1
–
Switching (1bit)
R
Thermo On/Off Status (Inverter Type Only)
0
–
Off, 1 - On
2.2.2
Controlling all units at a time
Property
EIS type
Signal
type
(R/W)
Description / Status
HW Error Com
1
– Switching (1bit)
R
HW Communication Status
0
– Communication OK, 1 – Communication ERROR
OnOff_All
1
– Switching (1bit)
R/W
Indoor Unit On/Off
0
– Off, 1 – On
Mode_All
14
– Counter (8bit)
R/W
Operation Mode
0
– Auto, 1 – Heat, 2 – Cool, 3 – Fan, 4 – Dry
DPT 20.105 (8bit)
R/W
Operation Mode
0
– Auto, 1 – Heat, 3 – Cool, 9 – Fan, 14 – Dry
DPT 1.100 (1bit)
R/W
Operation Mode
0
– Cool, 1 – Heat
Mode_All::Cool
1
– Switching (1bit)
R/W
0
–Inactive, 1–Active
Only one of these objects will be
set / read to “1” at the same time
(all objects will be updated on bus
upon a Mode change)
Mode_All::Heat
1
– Switching (1bit)
R/W
0
–Inactive, 1–Active
Mode_All::Fan
1
– Switching (1bit)
R/W
0
–Inactive, 1–Active
Mode_All::Auto
1
– Switching (1bit)
R/W
0
–Inactive, 1–Active
SetPoint_All
5
– Float (2byte)
R/W
Set Point
Temperature
(only integer numbers allowed)
16..30 ºC
Fan Speed_All
14
– Counter (8bit)
R/W
Fan Speed
0
– Low, 1 – Medium, 2 – High, 3 – Powerful
FanSpeed_All::Low
1
– Switching (1bit)
R/W
0
–Inactive, 1–Active
Only one of these objects will be
set / read to “1” at the same time
(all objects will be updated on bus
upon a FanSpeed change)
FanSpeed_All::Mid
1
– Switching (1bit)
R/W
0
–Inactive, 1–Active
FanSpeed_All::High
1
– Switching (1bit)
R/W
0
–Inactive, 1–Active
FanSpeed_All::Powerful
1
– Switching (1bit)
R/W
0
–Inactive, 1–Active
RemoconLock_All
1
– Switching (1bit)
W
Remote Controller Lock/Unlock
0
– Unlock, 1 - Lock