background image

Intesis

TM

 KNX 

– Mitsubishi Heavy Industries AC 

 

 

User’s Manual r1.2 eng

 

    

 

  

 

 

 

 

 

© HMS Industrial Networks S.L.U - All rights reserved 

This information is subject to change without notice

 

 

  URL    https://www.intesis.com  

 
 

                8 / 26

 

 

KNX interface of Intesis

TM

 

 

 

Description

 

Intesis

TM

 KNX - Mitsubishi Heavy Industries supports the KNX TP-1 (EIB) physical layer, as 

defined  in  the  KNX  standard.  It  behaves  as 

another

  device  of  the  KNX  system,  with  the 

same configuration and functional characteristics as other KNX devices. 
 
KNX TP-1 (EIB) bus provides a 30V DC current, which can even directly power certain low-
consumption KNX devices. Intesis

TM

 does not drain any significant current from the KNX bus 

- it has a separate own power supply. Another important electrical aspect is that the KNX 
TP-1  (EIB)  port  of  Intesis

TM

  is  optically  isolated  (~2500Vrms  AC)  from  all  its  other  ports 

(EIA232, EIA485, Ethernet) and power supply. 
 
At a logical level, all KNX devices feature an interface of communication objects, by which 
their functionality is abstracted. As a basic example, a  KNX interface of an AC indoor unit 

would  typically  consist  of  an  interface  of  datapoints  such  as  “On/Off”,  “Setpoint 
temperature”, “Operating mode”, etc.

 

 
Associations between communication objects from different  KNX devices are actually done 
by means of so-called group addresses. 
 
KNX  telegrams  within  a  working  KNX  installation  are  always  addressed  to  a  certain  KNX 
group  address.  Typically,  whenever  a  communication  object  on  a  KNX  device  changes  its 

value, the new value is updated to the bus, by sending a “write” telegram addressed to its 

associated  group  address.  The  rest  of  KNX  devices  in  the  installation  that  have  a 
communication object associated to this group address will act accordingly on reception of 
the new value. 
 
Other operations are possible. KNX devices can also decide to read the current value of the 

communication objects, by sending a “read” telegram to a certain group address (previously 

known to be associated to the targeted comm. object). This operation is performed by many 
devices  on  bus  start-up  or  recovery 

  in  this way,  the  device  gets  the  latest  value  of  the 

group addresses it has associated right from its start-up. 
 
Each  datapoint  defined  in  Intesis

TM

  KNX  configuration  needs  at  least  a  single  KNX  group 

address  associated  with  it.  This  group  address  will  be  used  either  for  sending  updates 

to 

KNX  of  the  datapoint  value  (that  have  been  generated  on  the  other  MHI  interface  of  the 
Intesis

TM

), or receiving updates 

from 

KNX of the datapoint value (that will be propagated to 

the MHI side in this case) 
 
From the point of view of KNX functionality, each datapoint of  Intesis

TM

 can hold following 

group address associations: 
 

 

A  single  KNX  group  address  with  which  update/write  telegrams  will  be  sent, 
whenever  the  datapoint  changes  (as  a  result  of  a  change  coming  from  the  other 
interface of Intesis

TM

, MHI in this case).  

 

 

One  or  more  KNX  group  addresses  from  which  this  datapoint  of  Intesis

TM

  will  be 

updated/written from the KNX installation (resulting in a change to the other side of 
Intesis

TM

, MHI in this case).  

 
 
 
A  single  KNX  group  address  from  which  Intesis

TM

  will  read  the  object  value  on  KNX  bus 

recovery / Intesis

TM

 start-up. 

Содержание Intesis INKNXMHI048O000

Страница 1: ...Gateway for integration of Mitsubishi Heavy Industries air conditioning systems into KNX TP 1 EIB control systems Application s Program Version 2 1 USER MANUAL Issue date 07 2012 r1 2 ENGLISH...

Страница 2: ...purposes and are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many...

Страница 3: ...rights reserved This information is subject to change without notice URL https www intesis com 3 26 Gateway for integration of Mitsubishi Heavy Industries air conditioning systems into KNX TP 1 EIB co...

Страница 4: ...tesisTM Device Connections 12 Connect to Mitsubishi Heavy Industries Interface 13 Connect to KNX Interface 14 Connect to PC LinkBoxEIB 14 Power Device 14 LinkBoxEIB Configuration monitoring tool for I...

Страница 5: ...he KNX system read and write in the communication objects Moreover IntesisTM includes all hardware required to manage control Mitsubishi Heavy Industries indoor units without extra components needed I...

Страница 6: ...m the corresponding action in the MHI s AC system In the continuous polling if no response is detected the corresponding virtual signal inside the gateway will be activated indicating communication er...

Страница 7: ...nk or Superlink II New Superlink Indoor Unit actual address range is 00 to 47 INKNXMHI128O000 Model supporting up to 128 indoor units For Superlink II New Superlink Indoor Unit actual address range is...

Страница 8: ...ew value is updated to the bus by sending a write telegram addressed to its associated group address The rest of KNX devices in the installation that have a communication object associated to this gro...

Страница 9: ...float 32bit floating type EIS10 16bit Counter 16bit raw EIS11 32bit Counter 32bit raw EIS13 ASCII char 8bit raw EIS14 8bit Counter 8bit raw ETS3 or ETS4 software tools are not used to configure Intes...

Страница 10: ...cument Write If the option of virtual ambient temperature and SetPoint is activated to be configured from extern KNX sensor see in section 4 2 1of this document Fan Speed 14 Counter 8bit R W Fan Speed...

Страница 11: ...an 4 Dry DPT 20 105 8bit R W Operation Mode 0 Auto 1 Heat 3 Cool 9 Fan 14 Dry DPT 1 100 1bit R W Operation Mode 0 Cool 1 Heat Mode_All Cool 1 Switching 1bit R W 0 Inactive 1 Active Only one of these o...

Страница 12: ...erface connector s description 1 KNX configuration Port C1 8 Reset button Non supported 2 Non supported C2 9 Superlink selector SLK New Superlink II Old Superlink I 3 Console serial port EIA232 10 A B...

Страница 13: ...ded for Superlink connection For prevention of electromagnetic noise malfunctions parallel wiring with the power line should be avoided Select the appropriate Superlink mode in the SLK selector If you...

Страница 14: ...ser Manual Two methods to connect to the PC can be used Ethernet Using the ETH port Figure 3 1 of IntesisTM How to check connectivity is explained in section 6 3 Serial cable Connect the IntesisTM dev...

Страница 15: ...l be covered Connections configuration To configure the IntesisTM connection parameters and to see the points list press on the Config button in the menu bar see Figure 4 1 The Mitsubishi Heavy Indust...

Страница 16: ...lay after a bus reset It is expressed in seconds IntesisIP interface configuration parameters Figure 4 4 IntesisIP interface configuration 1 IP Enter the KNX physical address for the gateway 2 NetMask...

Страница 17: ...expressed in seconds s and ranges can vary from 60 s to 600 s 9 Virtual ambient temperature and setpoint Meant to be enabled when you want the temperature provided by a KNX sensor to be the reference...

Страница 18: ...ossible signal codes 3 Signal Signal s descriptive name optional Useful to identify the signal The default descriptive name corresponds to the signal s code but can be edited or modified 4 EIS KNX dat...

Страница 19: ...binary file MHI Lbox containing the configuration for the gateway will be generated and saved also into the project folder b If NO is selected remember that the binary file with the project needs to b...

Страница 20: ...ing the system In order to force a specific value to a signal double click its row in the table This will display a dialog in which the desired value can be entered see Figure 4 8 Changing its value i...

Страница 21: ...older containing these files in external media once the installation process is finished This way you will be able to do future configuration changes in case of reinstallation of LinkBoxEIB due for ex...

Страница 22: ...esired installation site For your convenience check external enclosure measures see 7 before deciding where to place the IntesisTM device 3 Connect the communication cable coming from the KNX bus to t...

Страница 23: ...ation error in the Superlink network Check the Mitsubishi Heavy Industries Superlink network and its connections Table 6 1 IntesisTM LED status information 6 3 2 Software checking Once physical connec...

Страница 24: ...to change without notice URL https www intesis com 24 26 Mechanical Electrical characteristics 1 Device can be installed in any position 5 mm 195 mm 138 mm 10 mm 15 mm Figure 7 1 External dimensions P...

Страница 25: ...R HOST PAC Push buttons 1 x Reset Device Selectors 1 x SLK selector Console port EIA232 DB9 female DCE SELV Configuration Via console port 2 Firmware Allows upgrades via console port Operational tempe...

Страница 26: ...e on power supply at primary side 33 E33 Inverter primary current error 35 E35 Cooling overload operation 36 E36 Discharge pipe temperature error 37 E37 Outdoor heat exchanger temperature thermistor a...

Отзывы: