![HMS Networks Intesis INKNXMHI048O000 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/hms-networks/intesis-inknxmhi048o000/intesis-inknxmhi048o000_user-manual_2141906005.webp)
Intesis
TM
KNX
– Mitsubishi Heavy Industries AC
User’s Manual r1.2 eng
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
5 / 26
Description
Introduction
Intesis
TM
KNX
–
Mitsubishi Heavy Industries AC
is a communication gateway for the
integration of Mitsubishi Heavy Industries air conditioning (AC) systems into KNX TP-1
(EIB).
This gateway allows integrating a Mitsubishi Heavy Industries AC system inside a
supervision/control/automation system through PLC, SCADA and, in general, through any
device or system with a KNX TP-1 (EIB) interface.
The aim of this integration is to make accessible several Mitsubishi Heavy Industries air
conditioning indoor units communicating with the Superlink protocol as if they were part of
a KNX TP-1 (EIB) system. Therefore, the
Intesis
TM
KNX
acts as a KNX device in the KNX TP-
1 (EIB) interface, allowing the KNX system read and write in the communication objects.
Moreover, Intesis
TM
includes all hardware required to manage/control Mitsubishi Heavy
Industries indoor units without extra components needed.
Integration signals
Following is the list of parameters that can be monitored/controlled on the indoor units
using Intesis
TM
:
▪
For
each
indoor unit
in the system:
o
Communication Status (read-only)
o
On/Off (R/W)
o
Operation Mode (R/W)
o
SetPoint Temperature (R/W)
o
Fan Speed (R/W)
o
Remocon Lock/Unlock (R/W)
o
Louver Control (R/W)
o
Room Temperature (read-only)
o
Filter Sign Status (read-only)
o
Error Code (read-only)
o
Compressor Status (read-only)
o
Filter Sign Reset (write-only)
o
Remocon Error Reset (write-only)
o
Thermo On/Off Status (read-only)
Apart from these, the Intesis
TM
also implements some extra signals (functions):
▪
For
all
indoor units
1
in the system:
o
HW Communication Status (read-only)
o
On/Off (write-only)
o
Operation Mode (write-only)
o
SetPoint Temperature (write-only)
o
Fan Speed (write-only)
o
Remocon Lock/Unlock (write-only)
1