LD301 blinks 9 time.
Communication error
.
Is DC 35V being output at
terminals C and D? (Normally
,
DC 32.5-38.5V is output.)
Ye
s
Interface relay
Coil terminal
Contact terminal
Is DC 35V being output across R713?
Is DC 12V being supplied across
the control side (coil terminal) of
interface relay?
Is a voltage (at least 10V) being
generated between the contact
terminals of interface relay?
Check the interface curcuit.
Ye
s
Ye
s
No
No
Ye
s
D707 and C710 may be defective.
There is a defective section between the
12V output of switching power supply on
the main P
.W
.B. and interface relay (also,
check for contact with solder
, etc.).
Repalce the interface relay
.
No
0305E Pg 90-109
4/1/06, 11:01 AM
97
Содержание Summit RAC-70YH5
Страница 34: ... 32 INDOOR UNIT OUTDOOR UNIT WIRING DIAGRAM MODEL RAS 70YH5 RAC 70YH5 0305E Pg 28 32 4 1 06 10 50 AM 32 ...
Страница 36: ... 35 CIRCUIT DIAGRAM MODEL RAS 70YH5 0305E Pg 35 4 1 06 10 52 AM 1 ...
Страница 37: ... 37 CIRCUIT DIAGRAM MODEL RAC 70YH5 0305E Pg 37 4 1 06 10 53 AM 1 ...
Страница 39: ... 40 MODEL RAC 70YH5 MAIN P W B 0305E Pg 39 42 4 1 06 10 53 AM 40 ...
Страница 40: ... 41 MAIN P W B NF P W B CAPA P W B 0305E Pg 39 42 4 1 06 10 53 AM 41 ...
Страница 42: ... 43 51 53 53 55 57 49 29 66 22 0305E Pg 43 4 1 06 10 54 AM 1 ...
Страница 86: ... 94 6 Check the main P W B power circuit 0305E Pg 90 109 4 1 06 11 01 AM 94 ...
Страница 87: ... 95 CHECKING THE REMOTE CONTROLLER 0305E Pg 90 109 4 1 06 11 01 AM 95 ...
Страница 92: ... 100 0305E Pg 90 109 4 1 06 11 01 AM 100 ...
Страница 102: ...HITACHI PM NO 0305E Printed in Malaysia RAS 70YH5 RAC 70YH5 0305E cover 4 1 06 12 03 PM 2 ...