ModBus Data Listing
Append
ix
B
B–40
Note 1:
Assume that the inverter current rating is 1000 (for D002).
Note 2:
When the value is 10000 (100.0 seconds), a value in the second decimal place is
ignored.
—
— Write to EEPROM
W
00 .Motor constant calculation
01 . Set data storage in
EEPROM
Other... Motor constant recalcu-
lation and set data storage in
EEPROM
0900h
02304
0000,
0001,
other
—
—
(Reserved)
—
—
0901h
to
1000h
02305
to
4096
—
—
D102
— DC voltage monitoring
Displays the DC Bus voltage
1026h
04134
0 to 9999
0.1 V
D103
— BRD load factor monitor-
ing
Displays the running average
Dynamic Braking usage ratio
(%ED)
1027h
04135
0 to 1000
0.1 %
D104
— Electronic thermal
overload monitoring
Displays the motor electronic
thermal overload estimated
temperature ratio. If the value
reaches 100%, the inverter will
trip (E05)
1028h
04136
0 to 1000
0.1 %
—
(Reserved)
—
—
1029h
to
102Dh
04137
to
04141
—
—
Holding Registers, “D” Group Monitor Functions
Func. Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.
Содержание SJ700-004LFU2
Страница 2: ......
Страница 42: ......
Страница 162: ......
Страница 241: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 248: ......
Страница 278: ......
Страница 279: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 359: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 378: ......
Страница 390: ......