ModBus Mode Communications
Append
ix
B
B–32
Store New
Register Data
(ENTER
Command)
Neither the command (06h) to write data to a register nor the command (10h) to write data to
multiple registers can store the updates they made in the internal memory of the inverter.
Turning the inverter power off without storing the updates deletes them and restores the original
register settings. If you intend to store register updates in the internal memory of the inverter,
issue the Enter command as described below.
If you have updated a control constant, you must recalculate the motor constants. In such cases,
use register "0900h" for recalculation as described below.
Submitting an ENTER Command:
• Write any data in all memory (of a holding register at 0900h) by the Write in Holding
Register command [06h].
NOTE:
The ENTER command takes much time to run. You can check its progress by monitor-
ing the Data Writing signal (of a coil at 001Ah).
NOTE:
The service life of the storage element of the inverter is limited (to about 100,000 write
operations). Frequent use of the ENTER command may shorten its service life.
Write Data
Description
0000
Recalculate the motor constants
0001
Store the register data
Other
Recalculate the motor constants and store the register data
Содержание SJ700-004LFU2
Страница 2: ......
Страница 42: ......
Страница 162: ......
Страница 241: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 248: ......
Страница 278: ......
Страница 279: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 359: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 378: ......
Страница 390: ......