27
Chapter 6
Inverter setting concerning WOP
The example below explains parameter settings of WJ200 (Ver.2.0 or above) concerning
WOP.
Tab.9 The parameter of inverter related to WOP
No.
Code
Function name
Content
Setting parameter
1 F001
Output frequency
setting
You could set the frequency when
the frequency instruction is done
from the operator.
Start FQ
~
Max. FQ
2 A001
Frequency
source
Select the frequency instruction
source.
00: VR
01: Terminal
02: Operator
03: Modbus
04: Option
06: Pulse
07: EzSQ
10: Math
3 A002
Run command
source
Select the run/stop command
source.
01: Terminal
02: Operator
03: Modbus
04: Option
4 b031
Software lock
mode selection
It is a function to prevent the
change in data.
00: Lock(SFT)
01: Only FQ(SFT)
02: Lock
03: Only FQ
10: RUN chg mode
5 b037
Function code
display restriction
Select the mode of the parameter
displayed in the operator.
00: All
01: Utilize
02: User
03: Compare
04: Basic
05: Monitor
6 b038
Initial display
selection
Select the start display.
000: The last display after the [SET]
key be pressed.
001
~
060: Display set by
d001
~
d060
201: Display of F001
202: Monitor mode B of WOP
7 b081
Data R/W
selection
Restrict the data read/write by
operator.
00: Data read/write enable
01: Data read enable / write disable
02: Data read disable / write enable
03: Data read/write disable
8
b087
Stop key selection
Make the STOP key of operator
enable/disable.
00: Enable
01: Disable
02: Enable when reset a trip
9 b164
Automatic return
to the initial
display
It will change into the display which
set by initial display selection
(b038) automatically when no
operation to the operator within ten
minutes.
00: Enable
01: Disable
If it sets to 31(OPE) and the input is
turned on, the frequency instruction
and the run command source will
set to operator compulsorily.
31: Set to operator compulsorily
If it sets to 51(F-TM) and the input
is turned on, the frequency
instruction and the run command
source will set to terminal
compulsorily.
51: Set to terminal compulsorily
10
C001
~
C007
Intelligent Input
terminal function
It shows the display which set by
initial display selection (b038) when
it sets to 86(DISP) and the input is
turned on.
86: Display limitation
Chapter 6
Inverter setting concerning WOP