9
Chapter 3
Connection, wiring, and attaching
Before install the operator on the control panel, please fix with M3 screws from the back of
the control panel. (2 holes, the same measurement as figure 4, has to be made at first )
When connecting to the inverter, please use cable which is recommended. Otherwise, please
use the cable with appointed dimension.
Tab. 7 Recommended cable
Model
Content
ICS-1 1m
cable
ICS-3 3m
cable
Make sure to use a straight cable within 3m in length and 10BASE-T category 5 (CAT5) of
UTP or STP when the
cable is prepared by the customer.
(NOTE) UTP
(
Unshielded twist pair cable
)
, STP
(
Shielded twist pair cable
)
.
Chapter 3
Connection, wiring, and attaching
Fig. 4 Diagram for punched holes’ dimensions
2-M3 (Back side of WOP) Depth3.5mm
Punched hole diagram
for installation