PMML0251A rev.2 - 02/2013
Refrigerant piping & refrigerant charge
27
ENGLISH
Maximum refrigerant piping length
IVX Premium series
(m)
Outdoor Unit
3HP
4HP
5HP
6HP
8HP
10HP
Maximum piping Length be-
tween the outdoor unit and
the farthest indoor unit
Actual Length (L)
50
75
100
Equivalent Length (EL)
70
95
125
Total piping length
2 units (A+B+C)
60
85
100
115
3 units (A+B+C+D)
--
95
100
130
4 units
(A+B+C+D+E+F+G+)
--
95
100
145
Maximum piping line
after first branch
2 and 3 units (B, C, D)
10
15
4 units
(B+D, B+E, C+F, C+G)
--
10
15
Main piping length A
A > B, C, D, E, F, G
Maximum height difference
Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower.)
30 / 20
Maximum height difference Indoor / Indoor
10
Maximum height difference:
branch pipe/Indoor (2, 3 and 4 units system)
branch pipe/branch pipe (4 units system)
3
(B-C) / (B-D) / (C-D) / (C+G)-(B+E) / (C+G)-(B+D)
(C+F)-(B+E) / (C+F)-(B+D)
< 8
IVX Standard series
(m)
Outdoor Unit
4HP
5HP
6HP
8HP
10HP
Maximum piping Length
between the outdoor unit
and the farthest indoor
unit
Actual Length (L)
70
75
100
Equivalent Length (EL)
90
95
125
Total piping length
2 units (A+B+C)
80
85
100
115
3 units (A+B+C+D)
90
95
100
130
4 units
(A+B+C+D+E+F+G+)
90
95
100
145
Maximum piping line
after first branch
2 and 3 units (B, C, D)
10
15
4 units
(B+D, B+E, C+F, C+G)
10
15
Main piping length A
A > B, C, D, E, F, G
Maximum height difference
Outdoor / Indoor (H)
(Outdoor Unit is Higher / Lower.)
30 / 20
Maximum height difference Indoor / Indoor
3
Maximum height difference:
branch pipe/Indoor (2, 3 and 4 units system)
branch pipe/branch pipe (4 units system)
3
(B-C) / (B-D) / (C-D) / (C+G)-(B+E) / (C+G)-(B+D)
(C+F)-(B+E) / (C+F)-(B+D)
< 8
N O T E
The liquid piping and the gas piping must be of the same piping length and run along the same route.
Install the branch piping as much as possible near the indoor units
Install Multikits at the same horizontal level.
_PMML0251A_r2.indb 27
06/02/2013 9:05:04
Содержание RAS-10HNCE
Страница 2: ..._PMML0251A_r2 indb 2 06 02 2013 9 04 41 ...
Страница 46: ...PMML0251A rev 2 02 2013 46 Safety summary control device setting _PMML0251A_r2 indb 46 06 02 2013 9 05 17 ...
Страница 118: ...118 Sicherheitsübersicht steuerungseinstellungen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 118 06 02 2013 9 06 09 ...
Страница 154: ...154 Dépannage PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 154 06 02 2013 9 06 33 ...
Страница 226: ...226 PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 226 06 02 2013 9 07 28 ...
Страница 298: ...298 Problemen oplossen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 298 06 02 2013 9 08 18 ...
Страница 370: ...370 Αντιμετωπιση προβληματων PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 370 06 02 2013 9 09 06 ...
Страница 371: ..._PMML0251A_r2 indb 371 06 02 2013 9 09 06 ...
Страница 372: ...PMML0251A rev 2 02 2013 Printed in Spain _PMML0251A_r2 indb 372 06 02 2013 9 09 07 ...