PMML0251A rev.2 - 02/2013
34
Drain piping
14 DRAIN PIPING
14.1 DRAIN DISCHARGING BOSS
When the base of the outdoor unit is temporarily utilized as a
drain receiver and the drain water in it is discharged, this drain
boss is utilized to connect the drain piping.
Model
Applicable Model
DBS-26
H(V)N(P/C)E
Connecting procedure
1
Insert the rubber cap into the drain boss up to the extruded
portions.
2
Insert the boss into the unit base and turn approximately 40
degree counterclockwise.
3
Size of the drain boss is 32 mm (O.D.).
4
A drain pipe should be field-supplied.
N O T E
Do not use this drain boss set in a cold area, because the drain
water may freeze.This drain boss is not sufficient to collect all
the drain water. If collecting drain water is completely required,
provide a drain-pan that is bigger than the unit base and install it
under the unit with drainage.
Rubber cap
Drain Boss
Extruded portion
Drain pipe
Drain pipe
Drain hole
of Base
15.1 GENERAL CHECK
1
Ensure that the field-supplied electrical components (mains
power switches, circuit breakers, wires, connectors and wire
terminals) have been properly selected according to the elec-
trical data indicated. Make sure that they comply with national
and regional electrical codes.
2
Following the Council Directive 2004/108/EC(89/336/EEC),
relating to electromagnetic compatibility, next table indicates:
Maximum permissible system impedance Z
max
at the interface
point of the user’s supply, in accordance with EN61000-3-11
MODEL
Z max
(Ω)
MODEL
Z max
(Ω)
RAS-3HVNPE
0.39
-
RAS-4HVNPE
0.27
RAS-4HVNCE
0.27
RAS-5HVNPE
0.27
RAS-5HVNCE
0.27
RAS-6HVNPE
0.27
RAS-6HVNCE
0.27
RAS-4HNPE
-
RAS-4HNCE
-
RAS-5HNPE
-
RAS-5HNCE
-
RAS-6HNPE
-
RAS-6HNCE
-
RAS-8HNPE
-
RAS-8HNCE
-
RAS-10HNPE
-
RAS-10HNCE
-
3
Harmonics situation of each model regarding IEC 61000-3-2
and IEC 61000-3-12 is as follows:
MODELS SITUATION REGARDING IEC
61000-3-2 AND IEC 61000-3-12 Ssc
“xx”
MODELS
Ssc “xx”
(KVA)
Equipment complying with IEC 61000-3-2
(professional use
(*)
)
RAS-(4-6)HN(P/C)E
Equipment complying with IEC 61000-3-12
RAS-(3-6)HVN(P/C)E
-
Installation restrictions may be applied by au-
thorities regarding the power supply in relation
to harmonics
RAS-(8/10)HN(P/C)E
4
Check to ensure that the power supply voltage is /-
10% of the rated voltage.
5
Check to ensure that power supply has an impedance low
enough to warranty not reduce the starting voltage more than
85% of the rated voltage.
6
Check to ensure that the ground wire is connected.
7
Connect a fuse of specified capacity.
N O T E
Check and test to ensure that if there is more than one source of
power supply, that all are turned OFF.
C A U T I O N
Check
to ensure that screws for terminal block are tightly tight-
ened.
Check to ensure that the indoor fan and the outdoor fan have
stopped before electrical wiring work or periodical check is per-
formed.
Protect the wires, drain pipe, electrical parts, from rats or other
small animals. If not protected, rats may damage unprotected
parts, and at the worst, a fire will occur.
Wrap the accessory packing around the wires, and plug the wir-
ing connection hole with the seal material to protect the product
from any condensed water and insects.
Tightly secure the wires with the cord clamp inside the indoor
unit.
Lead the wires through the knockout hole in the side cover when
using conduit.
Secure the cable of the remote control switch with the cord clamp
inside the electrical box.
Electrical wiring must comply with national and local codes. Con-
tact your local authority in regards to standards, rules, regula-
tions, etc.
Check that the ground wire is securely connected.
Connect a fuse of specified capacity.
D A N G E R
Do not connect of adjust any wiring or connections unless
the main power switch is OFF.
Check that the earth wire is securely connected, tagged and
locked in accordance with national and local codes.
15 ELECTRICAL WIRING
_PMML0251A_r2.indb 34
06/02/2013 9:05:09
Содержание RAS-10HNCE
Страница 2: ..._PMML0251A_r2 indb 2 06 02 2013 9 04 41 ...
Страница 46: ...PMML0251A rev 2 02 2013 46 Safety summary control device setting _PMML0251A_r2 indb 46 06 02 2013 9 05 17 ...
Страница 118: ...118 Sicherheitsübersicht steuerungseinstellungen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 118 06 02 2013 9 06 09 ...
Страница 154: ...154 Dépannage PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 154 06 02 2013 9 06 33 ...
Страница 226: ...226 PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 226 06 02 2013 9 07 28 ...
Страница 298: ...298 Problemen oplossen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 298 06 02 2013 9 08 18 ...
Страница 370: ...370 Αντιμετωπιση προβληματων PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 370 06 02 2013 9 09 06 ...
Страница 371: ..._PMML0251A_r2 indb 371 06 02 2013 9 09 06 ...
Страница 372: ...PMML0251A rev 2 02 2013 Printed in Spain _PMML0251A_r2 indb 372 06 02 2013 9 09 07 ...