17 SAFETY SUMMARY & CONTROL DEVICE SETTING
Compressor Protection
High Pressure Switch:
This switch cuts out the operation of the compressor when the
discharge pressure exceeds the setting.
Fan Motor Protection
When the thermistor temperature is reached to the setting, motor
output is decreased.
The other way, when the temperature becomes lower, limitation
is cancelled.
Model
RAS-
3HVNPE
RAS-(4-6)HVN(P/C)E
RAS-(4-6)HN(P/C)E
RAS-(8-10)HN(P/C)E
For Compressor
Automatic Reset, Non-Adjustable (each one for each compressor)
Pressure Switches
-0.05
-0.05
-0.05
-0.05
High
Cut-Out
MPa
4.15
4.15
4.15
4.15
-0.15
-0.15
-0.15
-0.15
Cut-In
MPa
3.20±0.15
3.20±0.15
3.20±0.15
3.20±0.15
For Control
Fuse
1~ 230V 50Hz
A
40
50
(RAS-4HVNCE = 40)
3N~ 400V 50Hz
A
2 X 20
2 X 40
CCP Timer
min.
Non-Adjustable
Setting Time
3
3
3
3
For Condenser Fan Motor
Automatic Reset, Non-Adjustable (each one for each motor)
Internal Thermostat
Cut-Out
ºC
-
-
-
-
For Control Circuit
A
5
5
5
5
Fuse Capacity on PCB
18 TROUBLESHOOTING
Alarm Code Indication of Remote Control Switch:
Abnormal
Indoor Unit
No.
Abnormal
Ref. Cycle
No.
Alarm Code Model Code
Connected
No. of Indoor
Units
Alarm
Code
Model Code
Indication
Model
Heat-Pump
COOL MED
ADDS. RN
A/C
ALARM
Indicated
for a sec-
ond alter-
nately
COOL MED
ADDS. RN
A/C
ALARM
Inverter
Multi (Set-Free)
Cooling Only
Others
2, 3 and 4 indoor units
system
_PMML0251A_r2.indb 44
06/02/2013 9:05:16
Содержание RAS-10HNCE
Страница 2: ..._PMML0251A_r2 indb 2 06 02 2013 9 04 41 ...
Страница 46: ...PMML0251A rev 2 02 2013 46 Safety summary control device setting _PMML0251A_r2 indb 46 06 02 2013 9 05 17 ...
Страница 118: ...118 Sicherheitsübersicht steuerungseinstellungen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 118 06 02 2013 9 06 09 ...
Страница 154: ...154 Dépannage PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 154 06 02 2013 9 06 33 ...
Страница 226: ...226 PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 226 06 02 2013 9 07 28 ...
Страница 298: ...298 Problemen oplossen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 298 06 02 2013 9 08 18 ...
Страница 370: ...370 Αντιμετωπιση προβληματων PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 370 06 02 2013 9 09 06 ...
Страница 371: ..._PMML0251A_r2 indb 371 06 02 2013 9 09 06 ...
Страница 372: ...PMML0251A rev 2 02 2013 Printed in Spain _PMML0251A_r2 indb 372 06 02 2013 9 09 07 ...