PMML0251A rev.2 - 02/2013
Electrical wiring
35
ENGLISH
15.2.1 Setting of DIP Switches for Outdoor Unit
Quantity and Position of DIP Switches.
The location is as follows:
RAS-3HVNPE and RAS-(4-10)HVN(P/C)E
DSW1: For Test Run
Factory setting
DSW2: Optional Function Setting
Factory setting
Piping length ≤ 5m
Piping lenght ≥ 30m
Optional function setting
Optional function setting
1 2 3 4 5 6
ON
External input/output setting mode
The electrical wiring connection for the outdoor unit is
shown in figure below:
RAS-3HVNPE and
RAS-(4-6)HVN(P/C)E
RAS-(4-10)HN(P/C)E
Power supply
1~ 230V
Control cable (5V)
Power supply
3N~ 400V
Control cable (5V)
Table for Terminal Connection between units
Wiring
System
Units type
Connection of terminals
Power Supply
DC inverter
O.U. to O.U.
L1 to L1, L2 to L2, L3 to L3, N to N
I.U. to I.U.
L1 to L1, N to N)
Operating
DC inverter
O.U. to I.U. or I.U. toI.U.
1 to1, 2 to 2
Remote Control DC inverter
I.U. to I.U.
A to A, B to B
O.U.: Outdoor Unit; I.U.: Indoor unit
15.2 ELECTRICAL WIRING CONNECTION FOR OUTDOOR UNITS
_PMML0251A_r2.indb 35
06/02/2013 9:05:10
Содержание RAS-10HNCE
Страница 2: ..._PMML0251A_r2 indb 2 06 02 2013 9 04 41 ...
Страница 46: ...PMML0251A rev 2 02 2013 46 Safety summary control device setting _PMML0251A_r2 indb 46 06 02 2013 9 05 17 ...
Страница 118: ...118 Sicherheitsübersicht steuerungseinstellungen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 118 06 02 2013 9 06 09 ...
Страница 154: ...154 Dépannage PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 154 06 02 2013 9 06 33 ...
Страница 226: ...226 PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 226 06 02 2013 9 07 28 ...
Страница 298: ...298 Problemen oplossen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 298 06 02 2013 9 08 18 ...
Страница 370: ...370 Αντιμετωπιση προβληματων PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 370 06 02 2013 9 09 06 ...
Страница 371: ..._PMML0251A_r2 indb 371 06 02 2013 9 09 06 ...
Страница 372: ...PMML0251A rev 2 02 2013 Printed in Spain _PMML0251A_r2 indb 372 06 02 2013 9 09 07 ...