PMML0251A rev.2 - 02/2013
14
Transportation and handling
N O T E
The label for the vessel under PED are attached on the high pres-
sure vessel. The pressure vessel capacity and vessel category
are indicated on the vessel.
Location of High Pressure Switch
Compressor
N O T E
The high pressure switch is indicated on the electrical wiring di-
agram in the outdoor unit as PSH connected to printed circuit
board (PCB1) in the outdoor unit
Structure of High Pressure Switch
Contact Point
Pressure Detected
Connected to the electrical wire
D A N G E R
Do not change the high-pressure switch locally or change
the high pressure cut-out set value locally. If changed, it will
cause serious injury or death due to explosion.
Do not attempt to turn service valve rod beyond its stop.
6 BEFORE OPERATION
C A U T I O N
Supply electrical power to the system for approximately 12 hours be-
fore start-up or a long shutdown. Do not start the system immediately
after power supply, it may cause a compressor failure because the
compressor is not heated well.
When the system is started after a shutdown longer that approxi-
mately 3 months, it is recommended to check the system by your
service contractor.
Turn OFF the main switch when the system is to be stopped for a
long period of time: If the main switch is not turned OFF, electric-
ity will be used, because the oil heater is always energised during
compressor stopping.
Make sure that the outdoor unit is not covered with snow or ice.
If covered, remove it by using hot water (approximately 50°C). If
the water temperature is higher that 50 °C, it will cause damage
to plastic parts.
7 REMOTE CONTROLLER
It is advisable to use PC-ART or PC-ARF remote controller (both optional). For more information about it installation and operation,
please refer to its corresponding Installation and Operation Manuals.
5 TRANSPORTATION AND HANDLING
When hanging the unit, ensure a balance of the unit, check safety
and lift it up smoothly
Do not remove any packing materials.
Hang the unit under packing condition with two ropes.
For safety reasons ensure that the outdoor unit is lifted smoothly
and does not lean
Model
Gross Weight
(kg)
RAS-3HVNPE
77
RAS-(4-6)H(V)NPE
116
RAS-4H(V)NCE
78
Model
Gross Weight
(kg)
RAS-(5-6)H(V)NCE
90
RAS-8HN(P/C)E
149
RAS-10HN(P/C)E
151
RAS-3HVNP
RAS-(4-6)H(V)NPE
RAS-(4-6)H(V)NCE
RAS-(8-10)HN(P/C)E
0.7 -1.0 m
> 60º
_PMML0251A_r2.indb 14
06/02/2013 9:04:51
Содержание RAS-10HNCE
Страница 2: ..._PMML0251A_r2 indb 2 06 02 2013 9 04 41 ...
Страница 46: ...PMML0251A rev 2 02 2013 46 Safety summary control device setting _PMML0251A_r2 indb 46 06 02 2013 9 05 17 ...
Страница 118: ...118 Sicherheitsübersicht steuerungseinstellungen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 118 06 02 2013 9 06 09 ...
Страница 154: ...154 Dépannage PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 154 06 02 2013 9 06 33 ...
Страница 226: ...226 PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 226 06 02 2013 9 07 28 ...
Страница 298: ...298 Problemen oplossen PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 298 06 02 2013 9 08 18 ...
Страница 370: ...370 Αντιμετωπιση προβληματων PMML0251A rev 2 02 2013 _PMML0251A_r2 indb 370 06 02 2013 9 09 06 ...
Страница 371: ..._PMML0251A_r2 indb 371 06 02 2013 9 09 06 ...
Страница 372: ...PMML0251A rev 2 02 2013 Printed in Spain _PMML0251A_r2 indb 372 06 02 2013 9 09 07 ...