– 102 –
HOW TO OPERATE USING THE SERVICE SWITCH THE OUTDOOR UNIT
1. Turn off the power supply to outdoor unit and then turn on again.
2. Remove the electrical box cover.
LD303 (red) will light and the unit will operate in the forced cooling mode at this time.
Never operate the unit for
more than 5 minutes.
(Cautions)
(1) If interface signal (DC 35V) terminals C and D are not connected when the outdoor unit is in forced cool mode, the outdoor
unit defect indicator (LD301) will blink 9 times during operation to indicate communication error.
(2) If checking is done with the compressor connector disconnected, the unit will continue normal operation when the
electrical parts are normal, or it will repeat operating for approx. one minute and stop due to overload power limit cut,
or it will operate in the overload status.
Be sure to push the service switch again to stop the forced cool operation.
HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY
The operation method is the same as “How to operate using the connector to servicing the outdoor unit”.
1 The charging amount of 300g is equivalent to the load in normal operation.
Charge refrigerant of 300g
after vacuuming ( 1 )
Do not operate for more than 5
minutes
Parts to be prepared
(1) Reducing union
2/8” (6.35mm)
1/2” (12.7mm)
(2) Copper pipe (2/8” and 1/2”)
1. Connect the large dia. pipe side and small dia. pipe side service valves using a pipe.
Connect the small diameter
service value and the large
diameter service valve using the
reducing union and copper pipe
as shown on the right.
Electrical Box Cover
Service switch
(forced-cooling mode is set by
pressing for 1 second or more,
and stopped by pressing again.)
Self diagnosis lamps
(LD303, 302, 301)
Large dia. service valve
Reducing union
(2/8 and 3/8 )
Copper pipe
(2/8 )
Small diameter
service valve
Reversing
valve
Compressor
Outdoor unit
Содержание RAC-50DH7
Страница 30: ... 29 CIRCUIT DIAGRAM Wired Remote Control ...
Страница 31: ... 31 CIRCUIT DIAGRAM MODEL RAD 50DH7A RAD 60DH7A RAD 70DH7A ...
Страница 32: ... 33 CIRCUIT DIAGRAM MODEL RAC 50DH7 RAC 60DH7 RAC 70DH7 ...
Страница 35: ... 39 51 53 53 55 57 49 29 66 Heating ...
Страница 76: ... 86 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50DH7 RAC 60DH7 RAC 70DH7 ...
Страница 79: ... 89 2 Outdoor unit does not operate but receives remote infrared signal ...
Страница 82: ... 92 CHECKING THE REMOTE CONTROLLER ...
Страница 87: ... 97 16 ...
Страница 101: ...HITACHI PM NO 0411E Printed in Malaysia RAD 50DH7A RAC 50DH7 RAD 60DH7A RAC 60DH7 RAD 70DH7A RAC 70DH7 ...