– 27 –
COMPRESSOR MOTOR
Compressor Motor Specifications
!
CAUTION
When the Air Conditioner has been operated for a long time with the capillary tubes clogged or crushed or
with too little coolant, check the color of the refrigerant oil inside the compressor. If the color has been
changed conspicuously, replace the compressor.
V/R (YELLOW)
W/S (RED)
U/C (WHITE)
MODEL
COMPRESSOR MODEL
PHASE
SINGLE
RATED VOLTAGE
AC 220 ~ 240 V
RATED FREQUENCY
50 Hz
POLE NUMBER
4
CONNECTION
20
°
C
(68
°
F)
75
°
C
(167
°
F)
( )
RESISTANCE VALUE
RAC-50DH7/RAC-60DH7/RAC-70DH7
JU1015D4
2M = 1.05
U
V
W
WHITE
YELLOW
RED
2M = 1.268