![Hitachi RAC-50DH7 Скачать руководство пользователя страница 24](http://html.mh-extra.com/html/hitachi/rac-50dh7/rac-50dh7_service-manual_139700024.webp)
– 23 –
CONSTRUCTION AND DIMENSIONAL DIAGRAM
Note:
1. Servicing space of 100mm or more is required on the left and right sides of the indoor unit and also 50mm or
more space is required above the unit
2. Insulated pipes should be used for both the narrow and wide dia. pipes.
3. Piping length is within 20m
4. Height different of the piping between the indoor unit and the outdoor unit should be within 10m.
5. Power supply cord length is about 2m
6. Connecting cable 2.5mm dia. x 3 (AB Line), 1.6mm dia. x 2 (CD Line) is used for the connection.
D
C
B
A
L
N
D
C
B
A
Indoor Unit
Outdoor Unit
Connecting
Cord
Power
supply
cord
MODEL
RAD-50DH7A
RAD-60DH7A
RAD-70DH7A
Unit : mm
Wired remote controller
120
70
18