– 56 –
4. Room Temperature Thermistor Circuit
●
Fig. 4-1 shows the room temperature
thermistor circuit.
5
4
3
2
1
0
0
10
Fig. 4-2
20
30
40
0V
Room
temperature
thermistor
0V
5V
L301
Fig. 4-1
62
A
R305
C302
Microcomputer
Room
temp. input
V
oltage at
(V)
R301
A
●
The voltage at depends on the room
temperature as shown in Fig. 5-2.
A
3. Initial Setting Circuit (IC401)
●
When power is supplied, the microcomputer reads the data in IC401 (E
2
PROM) and sets the preheating
activation value and the rating and maximum speed of the compressor, etc. to their initial values.
●
Data of self-diagnosis mode is stored in IC401; data will not be erased even when power is turned off.
Fig. 3-1
Microcomputer
External ROM
SCL
SDA
0V
0V
0V
5V
5V
5V
C401
IC401 (E
2
PROM)
R404
R403
27
26
1
2
3
4
8
7
6
5
}
Содержание RAC-50DH7
Страница 30: ... 29 CIRCUIT DIAGRAM Wired Remote Control ...
Страница 31: ... 31 CIRCUIT DIAGRAM MODEL RAD 50DH7A RAD 60DH7A RAD 70DH7A ...
Страница 32: ... 33 CIRCUIT DIAGRAM MODEL RAC 50DH7 RAC 60DH7 RAC 70DH7 ...
Страница 35: ... 39 51 53 53 55 57 49 29 66 Heating ...
Страница 76: ... 86 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50DH7 RAC 60DH7 RAC 70DH7 ...
Страница 79: ... 89 2 Outdoor unit does not operate but receives remote infrared signal ...
Страница 82: ... 92 CHECKING THE REMOTE CONTROLLER ...
Страница 87: ... 97 16 ...
Страница 101: ...HITACHI PM NO 0411E Printed in Malaysia RAD 50DH7A RAC 50DH7 RAD 60DH7A RAC 60DH7 RAD 70DH7A RAC 70DH7 ...