– 49 –
Notes:
(1)
The sleep operation starts when the sleep key is pressed.
(2)
When the sleep key is set, the maximum compressor speed is limited to WSTD+2000/2, and the indoor fan is set
to “sleep Lo”.
(3)
If the operation mode is changed during sleep operation, the changed operation mode is set and sleep control
starts.
(4)
The indoor fan speed does not change even when the fan speed mode is changed. (Lo)
(5)
When defrosting is to be set during sleep operation, defrosting is engaged and sleep operation is restored after
defrosting.
(6)
When operation is stopped during sleep operation, the set temperature when stopped, as well as the time, continue
to be counted.
(7)
If the set time is changed during sleep operation, all data including set temperature, time, etc. is cleared and
restarted.
(8)
If sleep operation is canceled by the cancel key or sleep key, all data is cleared.
WMIN
1 min
Содержание RAC-50DH7
Страница 30: ... 29 CIRCUIT DIAGRAM Wired Remote Control ...
Страница 31: ... 31 CIRCUIT DIAGRAM MODEL RAD 50DH7A RAD 60DH7A RAD 70DH7A ...
Страница 32: ... 33 CIRCUIT DIAGRAM MODEL RAC 50DH7 RAC 60DH7 RAC 70DH7 ...
Страница 35: ... 39 51 53 53 55 57 49 29 66 Heating ...
Страница 76: ... 86 SELF DIAGNOSIS LIGHTING MODE MODEL RAC 50DH7 RAC 60DH7 RAC 70DH7 ...
Страница 79: ... 89 2 Outdoor unit does not operate but receives remote infrared signal ...
Страница 82: ... 92 CHECKING THE REMOTE CONTROLLER ...
Страница 87: ... 97 16 ...
Страница 101: ...HITACHI PM NO 0411E Printed in Malaysia RAD 50DH7A RAC 50DH7 RAD 60DH7A RAC 60DH7 RAD 70DH7A RAC 70DH7 ...