Logic Output Function
The Logic Output Function uses the inverter’s built-in logic feature. You can select any
two of the other nine intelligent output options for internal inputs (use C141 and C142).
Then, use C143 to configure the logic function to apply the logical AND, OR, or XOR
(exclusive OR) operator as desired to the two inputs.
[NDc]
t
C076
Master
Watchdog timer
Slave
Time-out
Alarm
=00 or 01
C077 =xx.xx sec.
Input States
[LOG] Output State
A Input
(C141 select)
B Input
(C142 select)
AND
(C143=00)
OR
(C143=01)
XOR
(C143=02)
0
0
0
0
0
0
1
0
1
1
1
0
0
1
1
1
1
1
1
0
C141
Logic function
AND, OR, XOR
Input A
RUN, FA1, FA2, OL, OD,
AL, Dc, FBV, NDc
Intelligent outputs used
as internal inputs:
C142
Input B
RUN, FA1, FA2, OL, OD,
AL, Dc, FBV, NDc
C143
[LOG]
Содержание L200 Series
Страница 2: ......
Страница 40: ......
Страница 186: ......
Страница 187: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 192: ......
Страница 209: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 256: ......
Страница 257: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 268: ......
Страница 269: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 273: ...L200 Inverter Appendix D D 5 L1 L2 L3 PE L200 inverter with book type filter M 3 ...