Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–10
The two diagrams below show input wiring circuits using the inverter’s in24V
supply. Each diagram shows the connection for simple switches, or for a field device
with transistor outputs. Note that in the lower diagram, it is necessary to connect
terminal [L] only when using the field device with transistors. Be sure to use the correct
SR/SK switch position shown for each wiring diagram.
L200
L
24V
+
–
SK
SR
SK
SR
PCS
Input
circuits
1
5
Logic GND
1
5
GND
Open collector outputs,
NPN transistors
Input
switches
Sinking Inputs, Internal Supply
SR/SK switch = SK position
Field device
L200
L
24V
+
–
SK
SR
SK
SR
PCS
Input
circuits
1
5
Common,
to [PCS]
1
5
GND
PNP transistor
sourcing outputs
Input
switches
Sourcing Inputs, Internal Supply
SR/SK switch = SR position
Field device
to PNP bias
circuits
Logic GND
Содержание L200 Series
Страница 2: ......
Страница 40: ......
Страница 186: ......
Страница 187: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 192: ......
Страница 209: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 256: ......
Страница 257: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 268: ......
Страница 269: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 273: ...L200 Inverter Appendix D D 5 L1 L2 L3 PE L200 inverter with book type filter M 3 ...