Using Intelligent Input Terminals
Oper
ations
and Monitor
ing
4–22
Software Lock
When the terminal [SFT] is turned ON, the data of all the parameters and functions
(except the output frequency, depending on the setting of B031) is locked (prohibited
from editing). When the data is locked, the keypad keys cannot edit inverter parameters.
To edit parameters again, turn OFF the [SFT] terminal input.
Use parameter B031 to select whether the output frequency is excluded from the lock
state or is locked as well.
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
15
SFT
Software Lock
ON
The keypad and remote programming devices
are prevented from changing parameters
OFF
The parameters may be edited and stored
Valid for inputs:
C001, C002, C003, C004,
C005
Required settings:
B031 (excluded from lock)
Notes:
•
When the [SFT] terminal is turned ON, only the
output frequency can be changed.
•
Software lock can include the output frequency by
setting B031.
•
Software lock by the operator is also possible
without the [SFT] terminal being used (B031).
Example (requires input configuration—see
page
):
See I/O specs on page
SFT
1
2
3
4
5
L
PCS
Содержание L200 Series
Страница 2: ......
Страница 40: ......
Страница 186: ......
Страница 187: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 192: ......
Страница 209: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 256: ......
Страница 257: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 268: ......
Страница 269: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 273: ...L200 Inverter Appendix D D 5 L1 L2 L3 PE L200 inverter with book type filter M 3 ...