ModBus Data Listing
Appendix B
B–34
B084
Initialization mode
(parameters or trip
history)
R/W Select the type of initialization
to occur, two option codes:
00... Trip history clear
01... Parameter initialization
02... Trip history clear and
parameter initialization
009Ah
0, 1, 2
—
B085
Country code for initial-
ization (not accessible
to ModBus)
—
Select default parameter values
for country on initialization.
Note: Write not allowed from
network.
009Bh
—
—
B086
Frequency scaling
conversion factor
R/W Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9
009Ch
1 to 999
0.1
B087
STOP key enable
R/W Select whether the STOP key
on the keypad is enabled, two
option codes:
00... enabled
01... disabled
009Dh
0, 1
—
B088
Restart mode after FRS
R/W Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency
detected from real speed of
motor (frequency matching)
009Eh
0, 1
—
B089
Monitor display select
for networked inverter
R/W Selects the parameter
displayed on the keypad
display when the inverter is
networked, 7 options:
01... Output frequency monitor
02... Output current monitor
03... Rotation direction
monitor
04... Process variable (PV),
PID feedback monitor
05... Intelligent input terminal
status
06... Intelligent output terminal
status
07... Scaled output frequency
monitor
00E9h
1 to 7
—
B091
Stop mode selection
R/W Selects how the inverter stops
the motor, two option codes:
00... DEC (decelerate and stop)
01... FRS (free run to stop)
00A0h
0, 1
—
“B” Group Fine Tuning Functions
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.
Содержание L200 Series
Страница 2: ......
Страница 40: ......
Страница 186: ......
Страница 187: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 192: ......
Страница 209: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 256: ......
Страница 257: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 268: ......
Страница 269: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 273: ...L200 Inverter Appendix D D 5 L1 L2 L3 PE L200 inverter with book type filter M 3 ...