B089: Monitor display select for networked inverter – When the L200 inverter is
controlled via network, the inverter’s keypad display can still provide Monitor Mode.
The D00x parameter selected by function B089 will be displayed on the keypad. See
“Local Monitoring During Network Operation” on page 3–8
for more details.
“B” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–FEF
(EU)
–FU
(USA)
Units
B088 Restart mode after FRS
Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00... Restart from 0Hz
01... Restart from frequency
detected from real speed of
motor (frequency matching)
✘
00
00
—
RUN FRS ZST
B089 Monitor display select
for networked inverter
Selects the parameter
displayed on the keypad
display when the inverter is
networked, 7 options:
01... Output frequency monitor
02... Output current monitor
03... Rotation direction
monitor
04... Process variable (PV),
PID feedback monitor
05... Intelligent input terminal
status
06... Intelligent output terminal
status
07... Scaled output frequency
monitor
✘
01
01
—
PANEL d001
B091 Stop mode selection
Selects how the inverter stops
the motor, two option codes:
00... DEC (decelerate and stop)
01... FRS (free run to stop)
✘
00
00
—
STP Slct DEC
B130 Over-voltage
LADSTOP enable
Pauses deceleration ramp when
DC bus voltage rises above
threshold level, in order to
avoid over-voltage trip.
Two option codes:
00... Disable
01... Enable
✘
00
00
—
OVLADSTOP OFF
B150 Carrier mode
Automatically reduces the
carrier frequency as the
ambient temperature increases.
Two option codes:
00... Disable
01... Enable
✘
00
00
—
Cr-DEC OFF
Содержание L200 Series
Страница 2: ......
Страница 40: ......
Страница 186: ......
Страница 187: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 192: ......
Страница 209: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 256: ......
Страница 257: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 268: ......
Страница 269: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 273: ...L200 Inverter Appendix D D 5 L1 L2 L3 PE L200 inverter with book type filter M 3 ...