L200 Inverter
xiii
Terminal Tightening Torque and Wire Size
The wire size range and tightening torque for field wiring terminals are presented in the
tables below.
Wire Connectors
WARNING: Field wiring connections must be
made by a UL Listed and CSA Certified ring lug
terminal connector sized for the wire gauge being
used. The connector must be fixed using the
crimping tool specified by the connector
manufacturer.
Input
Voltage
Motor Output
Inverter Model
Power Terminal
Wiring Size
Range (AWG)
Torque
kW
HP
ft-lbs
(N-m)
200V
0.2 1/4
L200-002NFEF/NFU
16
0.6
0.8
0.4
1/2
L200-004NFEF/NFU
0.55
3/4
L200-005NFEF
0.75
1
L200-007NFEF/NFU
14
0.9
1.2
1.1
1 1/2
L200-011NFEF
1.5
2
L200-015NFEF/NFU
12
2.2
3
L200-022NFEF/NFU
10
3.7
5
L200-037LFU
12
5.5
7 1/2
L200-055LFU
10
1.5
2.0
7.5
10
L200-075LFU
8
400V
0.4
1/2
L200-004HFEF/HFU
16
0.9
1.2
0.75
1
L200-007HFEF/HFU
1.5
2
L200-015HFEF/HFU
2.2
3
L200-022HFEF/HFU
3.0
4
L200-030HFEF
14
4.0
5
L200-040HFEF/HFU
5.5
7 1/2
L200-055HFEF/HFU
12
1.5
2.0
7.5
10
L200-075HFEF/HFU
Terminal Connector
Wiring Size
Range (AWG)
Torque
ft-lbs
(N-m)
Logic/Analog connector
30—16
0.16—0.19
0.22—0.25
Relay connector
30—14
0.37—0.44
0.5—0.6
Cable
Terminal (ring lug)
Cable support
Содержание L200 Series
Страница 2: ......
Страница 40: ......
Страница 186: ......
Страница 187: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 192: ......
Страница 209: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 256: ......
Страница 257: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 268: ......
Страница 269: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 273: ...L200 Inverter Appendix D D 5 L1 L2 L3 PE L200 inverter with book type filter M 3 ...