L200 Inverter
Appendix B
B–39
Note 1:
Assume that the inverter current rating is 10000 (for C041).
The following table lists the holding registers for the “H” Group Motor Constants.
C149
Output relay OFF delay
R/W Range is 0.0 to 100.0 sec.
00F7h
0 to 1000
0.1 sec
“C” Group Intelligent Terminal Functions
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.
“H” Group Motor Constants
Func.
Code
Name
R/W
Description
Network Data
Reg.
Range
Res.
H003
Motor capacity
R/W Thirteen selections:
0..... 0.20 kW
1..... 0.37 kW
2..... 0.40 kW
3..... 0.55 kW
4..... 0.75 kW
5..... 1.10 kW
6..... 1.50 kW
7..... 2.2 kW
8..... 3.0 kW
9..... 3.7 kW
10... 4.0 kW
11... 5.5 kW
12... 7.5 kW
00D9h
0 to 12
—
H203
Motor capacity, 2nd
setting
R/W
00DAh
0 to 12
—
H004
Motor poles setting
R/W Four selections:
2 / 4 / 6 / 8
00DBh
2, 4, 6,
8
1 pole
H204
Motor poles setting, 2nd
motor
R/W
00DCh
2, 4, 6,
8
1 pole
H006
Motor stabilization
constant
R/W Motor constant (factory set),
range is 0 to 255
00DDh 0 to 255
1
H206
Motor stabilization
constant, 2nd motor
R/W
00DEh
0 to 255
1
Содержание L200 Series
Страница 2: ......
Страница 40: ......
Страница 186: ......
Страница 187: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 192: ......
Страница 209: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 256: ......
Страница 257: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 268: ......
Страница 269: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 273: ...L200 Inverter Appendix D D 5 L1 L2 L3 PE L200 inverter with book type filter M 3 ...