Item
Operating
1
Not Operating
2
Shipping & Storage
3
Notes:
1.
Environmental specification for operation should be met before the storage system is powered on. Maximum
temperature of 90°F / 32°C should be strictly met at air system air inlet.
2.
Non-operating condition includes both packing and unpacking conditions unless otherwise specified.
3.
The system and components should be packed in factory packing for shipping and storing.
4.
No condensation in and around the drive should be observed under any conditions.
5.
The vibration specifications are applied to all three axes.
6.
See ASTM D999-01 The Methods for Vibration Testing of Shipping Containers.
7.
See ASTM D4728-01 Test Method for Random Vibration Testing of Shipping Containers.
8.
See ASTM D5277-92 Test Method for Performing Programmed Horizontal Impacts Using an Inclined Impact
Tester.
9.
See ASTM D6055-96 Test Methods for Mechanical Handling of Unitized Loads and Large Shipping Cases and
Crates.
10.
When FMDs (DKC-F810I-1R6FM/3R2FM) are installed.
Component weight, heat, airflow, and power consumption
The following table provides physical specifications of the individual VSP
G1000, VSP G1500, and VSP F1500 system components.
Component Name
Component Model No.
Weight
(lb/Kg)
Power
Consumption
(VA)
Heat
Output
Airflow
(m
3
/min)
Primary controller
DKC810I-CBXA
DKC810I-CBXAC
4
DKC810I-CBXE
4
312 /142
508
1
483
1
16.7(32°C)
25.9(40°C)
Secondary controller
DKC-F810I-CBXB
DKC-F810I-CBXF
308 / 140
435
1
413
1
16.7(32°C)
25.9(40°C)
SFF drive chassis
DKC-F810I-SBX
DKC-F810I-SBXC
4
315 / 143
674
1
640
1
9.4(32°C)
11.4(40°C)
LFF drive chassis
DKC-F810I-UBX
DKC-F810I-UBXC
4
299 / 136
674
1
640
1
6.2(32°C)
8.3(40°C)
FMD drive chassis
DKC-F810I-FBX
169 / 77
640
1
600
1
8.4
Service Processor
DKC-F810I-SVP
DKC-F810I-SVPC
4
8.8 / 4.0
75
Included in controller
chassis specs
Hub
DKC-F810I-HUB
5.1 / 2.3
10
Virtual storage director pair
(processor blades)
DKC-F810I-MP
DKC-F810I-MP2
DKC-F810I-MP2UGH
6.0 / 2.7
179
Cache path control adapter
DKC-F810I-CPEX
6.2 / 2.8
80
Cache module (16GB)
DKC-F810I-CM16G
0.022
4
Cache module (32GB)
DKC-F810I-CM32G
0.054
7
84
Site preparation
Hitachi Virtual Storage Platform G1000, G1500, and Virtual Storage Platform F1500 Hardware Guide
Содержание F1500
Страница 12: ...12 Preface Hitachi Virtual Storage Platform G1000 G1500 and Virtual Storage Platform F1500 Hardware Guide ...
Страница 50: ...50 Introduction Hitachi Virtual Storage Platform G1000 G1500 and Virtual Storage Platform F1500 Hardware Guide ...
Страница 106: ...106 Site preparation Hitachi Virtual Storage Platform G1000 G1500 and Virtual Storage Platform F1500 Hardware Guide ...
Страница 120: ...120 Troubleshooting Hitachi Virtual Storage Platform G1000 G1500 and Virtual Storage Platform F1500 Hardware Guide ...
Страница 132: ...132 Specifications Hitachi Virtual Storage Platform G1000 G1500 and Virtual Storage Platform F1500 Hardware Guide ...
Страница 182: ...182 System option modes Hitachi Virtual Storage Platform G1000 G1500 and Virtual Storage Platform F1500 Hardware Guide ...
Страница 204: ...204 Glossary Hitachi Virtual Storage Platform G1000 G1500 and Virtual Storage Platform F1500 Hardware Guide ...
Страница 207: ...Hitachi Virtual Storage Platform G1000 G1500 and Virtual Storage Platform F1500 Hardware Guide ...