Chapter 3 Programming
3
– 50
Cycle (interval) time of EtherCAT master
Recommended : Declaration in EtherCAT I/O mapping
Not recommended : Declaration in POU and referred from EtherCAT I/O mapping
Following information is based on our slave controller EH-IOCA.
Declaration in EtherCAT I/O mapping is about two times faster than declaration in POU.
EtherCAT cycle time depends on the total size of EtherCAT slaves. It increases about 70
s/word.
EtherCAT cycle time depends on the number of EtherCAT slaves. It increases about 700
s/unit.