Copyright © 2019, 2021, Hitachi, Ltd.
DKC910I
Hitachi Proprietary
[INST(IN)14-02-200]
Rev.5
INST(IN)14-02-200
(27)
Powering off, disabling the CE mode, and then powering on
(a) The message [INS4278i] is displayed.
Perform the procedures according to the message. At that time, refer
“
Disabling the jumper
used for initial installation (CEMD)
”
for the procedures to disable the CE mode.
(b) Close the Initial Setting window.
(c) Change the mode from [Initial Setting(Unlocked)] to [View Mode].
(28) Perform the following steps to reboot the SVP.
(a) Select [Start]-[Windows System], right-click the displayed [Command Prompt], and then select
[More]-[Run as administrator].
(b) In Command Prompt, enter
“
shutdown /r /t 0
”
and press the [Enter] key.
(29) Changing the set values for [Internal IP Address] to default
After the SVP reboot, reconnect the Maintenance PC to the SVP, because they are disconnected.
Check that the READY LED
on the DKC is turned on, and then change the set values
of [IP Address] and [Subnet Mask] for [Internal IP Address] to the default values.
[Default values]
IP Address: 126.255.254.15
Subnet Mask: 255.0.0.0
For the IP address change procedure, see
“
1. In case of SVP and DKC
”
“
Setting
IP address
”
.
NOTE: Select
“
SVP and DKC
”
for [Target] in the [Internal IP Address] settings.
(30) After the SVP reboot, reconnect the Maintenance PC to the SVP, because they are disconnected.
Check that the correct serial number of the storage system is displayed on the upper left of the SVP
window.