Copyright © 2019, 2021, Hitachi, Ltd.
DKC910I
Hitachi Proprietary
[INST(IN)09-02-20]
1. Cable types and selection criteria
(1) There are two types of X-path cables: copper and optical cables. The following table lists the cable
models.
Table 9-3 List of X-Path Cables
No.
Cable model
Cable length (m)
Quantity
Type
Remarks
1 DKC-F910I-MCC1/MCC1P
0.6
8
Copper
DKC-0 ~ HSNBX
(for CBXA)
2 DKC-F910I-MCC60/MCC60P
0.6
4
Copper
DKC-0 ~ HSNBX
(for CBX)
3 DKC-F910I-MCC2/MCC2P
0.45
8
Copper
DKC-1 ~ HSNBX
(for CBXB)
4 DKC-F910I-MCC45/MCC45P
0.45
4
Copper
DKC-1 ~ HSNBX
(for CBX2)
5 DKC-F910I-MPC5/MPC5P
5
8
Optical
6 DKC-F910I-MPC10/
SQSFP/SQSFPP
10
8
Optical
7 DKC-F910I-MPC20/
SQSFP/SQSFPP
20
8
Optical
8 DKC-F910I-MPC30/
SQSFP/SQSFPP
30
8
Optical
9 DKC-F910I-MPC1H/
SQSFP/SQSFPP
100
8
Optical
(2) The copper cables can be used only when all the following conditions are met. For the other cases,
use the optical cables.
(a) Connection between DKC-0 and HSNBX, and connection between DKC-1 and HSNBX.
(For connections between DKC-2 through 5 and HSNBX, use the optical cables.)
(b) DKC-0, DKC-1, HSNBX-0, and HSNBX-1 are adjacently installed in a 10U space in a rack in
the same layout shown below. The installation configuration is called the basic 10U.
Figure 9-11
Basic 10U Configuration
HSNBX-1
HSNBX-0
DKC-1
DKC-0
10U
2U
4U
4U
Basic 10U
Rev.0.1
INST(IN)09-02-20