Copyright © 2019, 2021, Hitachi, Ltd.
DKC910I
Hitachi Proprietary
[INST(IN)09-05-20]
Rev.4
INST(IN)09-05-20
7. Route the power cables.
8. Push in the plug of the power cable which has been inserted into the PDU again.
It may be loosened owing to a routing.
Route the power cables as shown in
.
9. Turn on all breakers of the PDUs.
Table 9-14
Chassis configuration and current specifications of each model
Model
Chassis configuration and current specifications
Total of current
consumption
DKC910I-
CBXA/CBX
PS-1
DKC
PS-2
7.2A
7.2A
PS-1
HSNBX
PS-2
1.2A
1.2A
PS-1
HSNBX
PS-2
1.2A
1.2A
CBXA/CBX
9.6A
9.6A
9.6 A
(7.2A (DKC) 1 +
1.2A (HSNBX) 2)
DKC-F910I-
CBXB/CBX2
PS-1
DKC
PS-2
7.2A
7.2A
CBXB/CBX2
7.2A
7.2A
7.2 A
(7.2A (DKC) 1)
DKC-F910I-SBX
PS-1
DBS2
PS-2
3.2A
3.2A
PS-1
DBS2
PS-2
3.2A
3.2A
PS-1
DBS2
PS-2
3.2A
3.2A
PS-1
DBS2
PS-2
3.2A
3.2A
SBX
12.8A
12.8A
12.8 A
(3.2A (DBS2) 4)
DKC-F910I-UBX
PS-1
DBL
PS-2
2.0A
2.0A
PS-1
DBL
PS-2
2.0A
2.0A
PS-1
DBL
PS-2
2.0A
2.0A
PS-1
DBL
PS-2
2.0A
2.0A
PS-1
DBL
PS-2
2.0A
2.0A
PS-1
DBL
PS-2
2.0A
2.0A
PS-1
DBL
PS-2
2.0A
2.0A
PS-1
DBL
PS-2
2.0A
2.0A
UBX
16.0A
16.0A
16.0 A
(2.0A (DBL) 8)
DKC-F910I-FBX
PS-1
DBF3
PS-2
3.1A
3.1A
PS-1
DBF3
PS-2
3.1A
3.1A
PS-1
DBF3
PS-2
3.1A
3.1A
PS-1
DBF3
PS-2
3.1A
3.1A
FBX
12.4A
12.4A
12.4 A
(3.1A (DBF3) 4)
DKC-F910I-NBX
PS-1
DBN
PS-2
4.0A
4.0A
PS-1
DBN
PS-2
4.0A
4.0A
PS-1
DBN
PS-2
4.0A
4.0A
PS-1
DBN
PS-2
4.0A
4.0A
NBX
16.0A
16.0A
16.0 A
(4.0A (DBN) 4)