4 Start-up
F3 AIO 8/4 01
Page 42 of 56
HI 800 161 E Rev. 2.00
NOTE
Overload, failure due to improperly set voltage (8.2 V / 26 V)!
Failure to comply with these instructions can damage the electronic components.
Prior to start-up, set the Transmitter Supply[01] system parameter to 1 (8.2 V). If the
shunt adapter has been overloaded, it must be replaced.
Switching Thresholds of the Analog Inputs
With the shunt adapter Z 7309, the current measurement of 0/4…20 mA is set at a resolution of
2000 digits.
The switch-on and switch-off thresholds, the open-circuit (OC) and short-circuit (SC) thresholds
and the corresponding fault reaction must be configured in the user program. The line
resistance has already been taken into account with the limits.
Switching
thresholds
Range of 2000 digits
1)
Description
NAMUR proximity switches in accordance with EN 60947-5-6
Switch-on threshold
L
H
1.75 mA [175 digits]
Transition from Low to High
Switch-off threshold
H
L
1.55 mA [155 digits]
Transition from High to Low
OC Limit
0.20 mA [20 digits]
Fault reaction to be configured:
Set the input value to faulty.
SC Limit
10.86 mA [1086 digits]
Fault reaction to be configured:
Set the input value to faulty.
SN / S1N proximity switches from Fuchs
Switch-on threshold
L
H
2.45 mA [245 digits]
Transition from Low to High
Switch-off threshold
H
L
2.25 mA [225 digits]
Transition from High to Low
OC Limit
0.20 mA [20 digits]
Fault reaction to be configured:
Set the input value to faulty.
SC Limit
5.63 mA [563 digits]
Fault reaction to be configured:
Set the input value to faulty.
1)
Verify the values of the proximity switches actually in use.
Table 35: Thresholds for the Inputs with Proximity Switches
Содержание HIMatrix F3 AIO 8/4 01