3 Product Description
F3 AIO 8/4 01
Page 24 of 56
HI 800 161 E Rev. 2.00
3.6
Product Data
General
Response time
≥
20 ms
Ethernet interfaces
2 x RJ-45, 10BASE-T/100BASE-Tx with integrated switch
Operating voltage
24 VDC, -15...+20 %, r
PP
≤
15 %,
from a power supply unit with safe insulation
in accordance with IEC 61131-2
Current input
max. 0.8 A (with maximum load)
Idle: approx. 0.4 A at 24 V
Fuse (external)
10 A time-lag (T)
Back-up battery
None
Operating temperature
0...+60 °C
Storage temperature
-40...+85 °C
Type of protection
IP20
Max. dimensions
(without plug)
Width: 207 mm (with housing screws)
Height: 114 mm (with fixing bolt)
Depth: 97 mm (with earthing rail)
Weight
approx. 1 kg
Table 16: Product Data
Analog inputs
Number of inputs
8 (non-galvanically separated)
Nominal range
0...+10 VDC,
0/4...+20 mA with 500
shunt
Operating range
-0.1...+11.5 VDC,
-0.4...+23 mA with 500
shunt
Input resistance
> 2 M
Source resistance input
of the input signal
500
Digital resolution
12-bit
Measurement accuracy at
25 °C, max.
0.1 % of final value
Metrological accuracy on full
temperature, max.
0.5 % of final value
Temperature coefficient, max.
0.011 %/K of final value
Safety-related accuracy, max.
2 % of final value
Measured value refresh
once per cycle of the controller
Sampling time
ca. 45 µs
Table 17: Specifications for the Analog Inputs