F3 AIO 8/4 01
4 Start-up
HI 800 161 E Rev. 2.00
Page 35 of 56
System parameter
Data type R/W
Description
Transmitter Voltage[01]
USINT
W
Switching of the transmitter supply for each group:
1 = 8.2 V
2 = 26.0 V
Table 29: SILworX - System Parameters for Analog Inputs,
Module
Tab
4.3.2.2
Tab AI 8: Channels
The
AI 8: Channels
tab contains the following system variables.
System
parameter
Data
type
R/W Description
-> Error Code
[BYTE]
BYTE
R
Error codes for the analog input channels
Coding
Description
0x01
Fault in the analog input module
0x02
Out of the defined limit values.
0x04
A/D converter faulty, measured values invalid
0x08
Measured value out of the safety-related accuracy
0x10
Measured value overflow
0x20 Channel
not
operating
0x40
Address error of both A/D converters
-> Value [INT]
INT
R
Analog value for each channel
INT
from 0...+2000 (0...+10 V)
The validity depends on
AI.Error Code
Channel Used
[BOOL] ->
BOOL W Channel
configuration:
1 = operating
0 = not operating
Threshold LOW
[INT] ->
INT
W
Voltage range upper limit for low level ->
Underflow [BOOL]
Limit Value HIGH
[INT] ->
INT
W
Voltage range low limit for high level
-> Overflow [BOOL]
Transmitter Used
[BOOL] ->
BOOL
W
AI channel used with transmitter supply:
1 = used
0 = not used
-> Underflow
[BOOL]
BOOL R Underflow
-> Value [INT]
in accordance with
Limit Value LOW [INT] ->
The validity depends on
AI.Error Code
-> Overflow
[BOOL]
BOOL R Overflow
-> Value [INT]
in accordance with
Limit Value HIGH [INT] ->
The validity depends on
AI.Error Code
Table 30: SILworX - System Parameters for Analog Inputs,
AI 8: Channels