4 Start-up
F3 AIO 8/4 01
Page 38 of 56
HI 800 161 E Rev. 2.00
4.4.3
Analog Inputs F3 AIO 8/4 01
System Signal
R/W
Description
Mod.SRS [UDINT]
R
Slot number (System Rack Slot)
Mod. Type [UINT]
R
Type of module, target value: 0x001E [30
dec
]
Mod. Error Code
[WORD]
R Module
error
code
Coding
Description
0x0000
I/O processing, if required with errors
see other error codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: invalid configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not plugged in
AI.Error Code
[WORD]
R
Error codes for all analog inputs
Coding
Description
0x0001 Module
fault
0x0004
Time monitoring of conversion faulty
0x0008
FTT test: Walking bit of data bus faulty
0x0010
FTT test: Error while checking coefficients
0x0020
FTT test: Operating voltages faulty
0x0040
A/D conversion faulty (DRDY_LOW)
0x0080
Cross links of MUX faulty
0x0100
Walking bit of data bus faulty
0x0200
Multiplexer addresses faulty
0x0400
Faulty operating voltages
0x0800
Measuring system (characteristic) faulty (unipolar)
0x1000
Measuring system (final values, zero point) faulty
(unipolar)
0x8000
A/D conversion faulty (DRDY_HIGH)
AI[xx].Error Code
[BYTE]
R
Error codes for the analog input channels
Coding
Description
0x01
Fault in the analog input module
0x02
Out of the defined limit values.
0x04
A/D converter faulty, measured values invalid
0x08
Measured value out of the safety-related accuracy
0x10
Measured value overflow
0x20 Channel
not
operating
0x40
Address error of both A/D converters
AI[xx].Value
[INT]
R
Analog value for each channel
INT
from 0...+2000 (0...+10 V)
The validity depends on
AI[xx].Error Code
AI[xx].Used [BOOL]
W
Channel configuration:
1 = operating
0 = not operating
AI[xx].Transmitter
Used
[BOOL]
W
AI channel used with transmitter supply:
1 = used
0 = not used
Содержание HIMatrix F3 AIO 8/4 01