4 Start-up
F3 AIO 8/4 01
Page 40 of 56
HI 800 161 E Rev. 2.00
4.4.4
Analog Outputs F3 AIO 8/4 01
System signal
R/W
Description
Mod.SRS [UDINT]
R
Slot number (System Rack Slot)
Mod. Type [UINT]
R
Type of module, target value: 0x0069 [105
dec
]
Mod. Error Code
[WORD]
R Module
error
code
Coding
Description
0x0000
I/O processing, if required with errors, see other error
codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: invalid configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not plugged in
AO.Error Code
[WORD]
R
Error codes for the analog output channels
Coding
Description
0x0001 Module
fault
0x0002
Safety switch 1 faulty
0x0004
Safety switch 2 faulty
0x0008
FTT test of test pattern faulty
0x0010
FTT test: Error while checking coefficients
0x0400
FTT test: 1st temperature threshold exceeded
0x0800
FTT test: 2nd temperature threshold exceeded
0x2000
Status of safety switches
0x4000
Active shutdown via watchdog faulty
AO
xx
.Error Code
[BYTE]
R
Error codes for the analog output channels
Coding
Description
0x01
Fault in the analog output unit
0x80
AO [xx].Value
out of specified range
AO[xx].Value [INT]
W
Output value of AO channels:
Current characteristic curve: 0...+2000 (0...+20 mA)
Current characteristic curve: -2000...0 (0 mA)
Before being normalized, the values are checked for plausibility.
Current characteristic curve:
Values
<
0:
are normalized to 0
Values < intermediate data point LOW:
Normalization with intermediate data point LOW
Values > intermediate data point HIGH:
Normalization with intermediate data point HIGH
Outputs must not be used as safety-related outputs!
AO[x].Used [BOOL]
W
Channel configuration
1 = Channel operating
0 = Channel not operating
Table 34: ELOP II Factory - System Signals for the Analog Outputs