4 Start-up
F3 AIO 8/4 01
Page 36 of 56
HI 800 161 E Rev. 2.00
4.3.3
Analog Outputs F3 AIO 8/4 01
The following tables present the statuses and parameters for the output module (AO 4) in the
same order as given in the Hardware Editor.
4.3.3.1
Tab
Module
The
Module
tab contains the following system parameters:
System parameter
Data
type
R/W
Description
AO.Error Code
WORD
R
Error codes for all analog outputs
Coding
Description
0x0001 Module
fault
0x0002
Safety switch 1 faulty
0x0004
Safety switch 2 faulty
0x0008
FTT test of test pattern faulty
0x0010
FTT test: Error while checking coefficients
0x0400
FTT test: 1st temperature threshold exceeded
0x0800
FTT test: 2nd temperature threshold exceeded
0x2000
Status of safety switches
0x4000
Active shutdown via watchdog faulty
Module Error Code
WORD
R
Module error code
Coding
Description
0x0000
I/O processing, if required with errors, see
other error codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: invalid configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module SRS
UDINT
R
Slot number (System Rack Slot)
Module Type
UINT
R
Type of module, target value: 0x0069 [105
dec
]
Table 31: SILworX - System Parameters for Analog Outputs,