Slot PLC NPLC-C100 | Hardware Installation
DOC120112UM02EN | Revision 2 | English | 2014-01 | Released | Public
© Hilscher, 2009-2014
6.2
Internal and External Power Supply
Note:
Hardware revision 3 of the slot PLC NPLC-C100 can be supplied
via the PCI bus only with 5 V. Hardware revision 4 of the slot PLC NPLC-
C100 can be supplied via the PCI bus with 3.3 V respectively 5 V.
The slot PLC can be supplied by 5 V or 3.3 V (via PCI) or by an additional
external supply voltage of 24 VDC. The permitted voltage range for external
powering is 18 … 30 V. If the external supply voltage reaches a level below
13 V, then the supply of the slot PLC from the external supply voltage is
switched off.
6.3
Reset Behaviour
The slot PLC has no connection via the PCI bus to the PC reset signal.
This means that a reset of the PC for example when using the front panel
reset button of the computer does not influence the slot PLC behavior.
The PowerOn reset will be served from both power sources (internal und
external).
6.4
RUN/STOP Switch
The PLC program’s operating condition in the slot PLC can be changed
using the switch at the front of the slot PLC and may get the status.
Position
Function
RUN
The loaded PLC program is executed cyclically.
STOP
The cyclic execution of the PLC program is stopped. Loading a new PLC
program or a firmware update is possible in this state.
Table 11: RUN/STOP Switch
6.5
LEDs
The meaning of the LED signals depends on the used firmware and the
embedded PLC type.
For a firmware with CoDeSys: The meaning of the LED is described in the
manual ‚netPLC with CoDeSys, commissioning’.