Appendix
30/36
Slot PLC NPLC-C100 | Hardware Installation
DOC120112UM02EN | Revision 2 | English | 2014-01 | Released | Public
© Hilscher, 2009-2014
10 Appendix
10.1 Memory Card
The slot PLC “NPLC-C100” device can be set back to factory settings with
a micro SD card and the base firmware on it.
Requirements
The memory card can have up to 4 GB storage capacity.
The memory card must be formatted in the FAT16 format (no FAT32).
The HDSC format is not supported.
Preparation
Copy all files from the directory
"Firmware\...\Memory Card Image"
including the file STARTUP.INI and the directory BACKUP and all
subdirectories onto an empty micro SD card to the card's root directory.
Procedure
1. Have the SD card ready with the copied image
2. Power down the PC with the slot PLC inserted. If used, switch off the
external power supply.
3. Insert the card into the SD card slot till it clicks into place
4. Re-Power the PC
The device loads the base firmware and indicates this by the following
states of the SYS LED: Fast change between green and yellow (for
appr. 8 s), then yellow on (for appr. 10 s), then off for a short moment
and finally it turns to green on.
The device then has factory settings.
5. Remove the SD card from the SD card slot