Design-In - Mechanical Aspects
37/78
COMX Communication Modules | Design Guide
DOC100901DG18EN | Revision 18 | English | 2013-12 | Released | Public
© Hilscher, 2002-2013
2.7.4.2
COMX 50CA-CCS
The following table shows the meaning of the address and baudrate switch for COMX 50.
CC-Link Slave
Station Address
Baudrate
Station address = Value * 16 + Value * 1
Value range for
Station address:
1 … 64
0 … 4 = valid address
5, 6, 7, 8, 9, A … F = invalid
address, error
0, 1, …, 8, 9, A, …, F = valid
address
0 = 156 kBaud
1 = 625 kBaud
2 = 2,5 MBaud
3 = 5 MBaud
4 = 10 MBaud
5 ... F = Invalid, error
Table 15: Meaning of the Address and Baudrate Switch of COMX 50CA-CCS
Example: For CC-Link station address 18 set the left switch to 1 and the middle switch to 2. For
baudrate 156 kBaud set the right switch to 0.
Depending on the configuration parameter ‘Number of stations’, the value range for station address
is:
Number of Stations
Value Range for Station Address
1
1 … 64
2
1 … 63
3
1 … 62
4
1 … 61
Table 16: Value Range for Station Address depending on Number of Stations