Design-In - Mechanical Aspects
36/78
COMX Communication Modules | Design Guide
DOC100901DG18EN | Revision 18 | English | 2013-12 | Released | Public
© Hilscher, 2002-2013
2.7.4
CC-Link Slave
2.7.4.1
COMX 10CA-CCS and COMX 10CN-CCS
The following table shows the meaning of the address and baudrate switches for COMX 10.
CC-Link Slave
Station Address
Baudrate
Station address = Value * 10 + Value * 1
Value range for
Station address:
1 … 64
0 … 6 = valid address
7, 8, 9 = invalid address, error
0, 1, …, 8, 9 = valid address
0 = 156 kBaud
1 = 625 kBaud
2 = 2,5 MBaud
3 = 5 MBaud
4 = 10 MBaud
5 ... 9 = Invalid, error
Table 13: Meaning of the Address and Baudrate Switch of COMX 10CA-CCS and COMX 10CN-CCS
Example: For station address 12 set the left switch to 1 and the middle switch to 2. For baudrate
156 kBaud set the right switch to 0.
Depending on the configuration parameter ‘Number of stations’, the value range for station address
is:
Number of Stations
Value Range for Station Address
1
1 … 64
2
1 … 63
3
1 … 62
4
1 … 61
Table 14: Value Range for Station Address depending on Number of Stations