EURO 46 V10 Programming Manual
No
Input Types
Operation
21
Entry Shock Input
Active when system set. Works in conjunction with EE input type for detection of forced entry.
This input type is designed specifically for use with systems installed using BS8243 option 6.4.5.
This input type is always used in conjunction with an ‘Entry/Exit’ input. The ‘Entry/Exit’ input is a
door contact on the initial entry door, and the ‘Entry Shock’ input is a non-latching shock sensor
fitted to the door frame in the vicinity of the lock. If the initial entry door is subjected to gross
attack and forced open, then at the expiry of entry time only one further intruder input need to
be activated to signal a sequentially confirmed alarm – the ‘Entry Shock’ input counts as the first
to alarm. The ‘Entry/Exit’ door contact must be opened with 10 seconds of the shock detector
triggering for the ‘Entry Shock’ response to apply. Triggering the ‘Entry Shock’ input in isolation will
not generate an alarm of any kind.
22
Input Line Fail
Active when fail.
Will give a line fault alarm, and will signal Telecom line fault signal on expiry of
line fault timer. Works in conjunction with CCTV input.
23
Keyswitch Pulsed*
Accepts input from key-switch (or equivalent) to set/unset the areas assigned to it. Requires
momentary action switch to toggle set/unset state.
29
Interior
Active when set.
Audible response: full communicator – intruder and unconfirmed signals. Will
send interior event when using Contact ID /Contact ID IP.
32
Flood
Active when set or unset.
This input type operates as a 24hr input, any inputs that are
programmed for ‘Flood’ will activate the external siren. Full communicator: intruder and
unconfirmed signals, flood event sent via Contact ID / Contact ID IP.
39
CCTV
Active at all times.
No audible or communicator response
If the input line fail is active, the system will signal CID/SIA events for perimeter alarm and the
CCTV input will open.
40
Perimeter
Active when set.
Audible response: full communicator – intruder and unconfirmed signals. Will
send perimeter event when using Contact ID /Contact ID IP.
41
Keybox
Export
: Similar to switcher input, but sends a Contact ID event of ‘keybox’
42
Medical
Sends a medical Contact ID event when activated.
43
Final Exit 2
This is useful for programming different entry times for the front door and the back door of a house
for example. See ‘Final exit’ listed above - for more details.
#
These inputs cannot be bypassed.
*
Use of inputs 20 and 23 will make the system unable to comply with EN50131-1 Security Grade 2
and 3.
$
Ensure that these inputs are used on an entry/exit route